2. Connection with power supply and barrier built into receiver.
Output: Standard 4 - 20 mA loop
Intrinsically safe
Barrier Parameters.
Uo(Voc)
=< 30 V
Io(Isc)
=< 120 mA
Po(Pmax) =< 0.84 W
Ca>Sum(Ci)+Ccable
La>Sum(Li)+Lcable
Ambient temperature limits
T4: -40 to + 85 deg. Celcius
T6: -40 to + 60 deg. Celcius
Warning:
Substitution of components may impair intrinsic safety.
The Transmitters must be installed in a suitable enclosure to meet installation
codes stipulated in the Canadian Electrical Code (CEC).
533XQC03.DOC
2006-01-04
Transmitter
Power Supply
built into
CSA approved
Receiving
Instrument
+
-
5331D or
5333D or
5335D
1
2
5331D or
6
3
5333D
5
4
SENSOR
5335D
Rev. AB
53 3 3 V 1 1 0 - I N
Terminal: 1-2
Ui(Vmax) = 30 V
Ii(Imax)
= 120 mA
Pi
= 0.84 W
Ci
= 1 nF
Li
= 10 uH
Terminal: 3,4,5,6
Only passive, or non-energy
storing devices such as
RTD's and Thermocouples
may be connected.
Terminal: 3,4,5,6
Uo(Voc) = 9.6 V
Io(Isc)
= 28 mA
Po
= 67.2 mW
Co(Ca)
= 3.5 uF
Lo(La)
= 35 mH
Non-
hazardous
location
max. 250 V
Hazardous
Locations /
Sécurité
Intrinséque
2/2
19