Connect the batteries to the
power supply terminals (3)
using the correct wire complete
with protection with fuse.
Be careful with the battery
polarity during the
connection.
When fitted inside the F115/8A (BTicino) enclosure, the device must be kept away from water drips and sprays.
The following table gives the maximum absorption which the system must have depending on the battery installed
and the life-time level required.
In all cases the maximum absorption must not exceed 700 mA.
lifetime when
there is
a power cut
Install the container
closing covers
type of battery installed
7,2 Ah
24 h
110 mA
15 h
180 mA
8 h
340 mA
4
4
If you want to protect the battery
compartment, connect the contact on the
container item F115/8B (BTicino) (4) to a
tamper line.
12 Ah
24 Ah
190 mA
380 mA
300 mA
600 mA
560 mA
700 mA