FEATURES
4
8
FIG.
11
1. Cabinet
2. Air Discharge
3. Vertical Air
Deflector
(Horizontal Louver)
4. Air Intake
(Inlet Grille)
5. Air Filter
6. Front Grille
7. Control Panet
8. Power Cord
9. Evaporator Coil
10. Condenser
1 1. Compressor
12. Base pan
13. Brace
14. Side Louver
USING THE AIR CONDITIONER
To reduce the risk of fire, electric
shock, or injury to persons, read the important
SAFETY instructions section before operating this
appliance.
To begin operating the air conditioner
after
installation, follow
these steps:
1. Plug in the air conditioner.
(To prevent electrical
hazards, do not use an extension cord or an
adapter plug.)
2. Set the exhaust vent to the CLOSE position.
3. Set the TEMP Control to the coolest setting.
4. Set the MODE control at the highest COOL level.
5. Adjust the louvers for comfortable air flow.
6. Once the room has cooled, adjust the TEMP and
Mode ControI to the setting you find most
comfortabIe.
NOTE : If the air conditioner is turned off, wait 3
minutes before restarting. This allows pressure
inside the compressor to equalize. Failure to wait 3
minutes before restarting may cause inefficient
operation.
if you move the TEMP Control to a warmer, then
immediately back to a cooler setting, the unit will
shut off. Wait 3 minutes before restarting.
VENT
CONTROL
The Vent ControI alIows the air conditioner to
either recirculate inside air (CLOSE) or exhaust
air to the outside (OPEN). (FIG. 12)
• The CLOSE position is used when maximum
cooling is desired. It may atso be used for air
recirculation without cooling when the air
conditioner is set in the FAN position.
• The OPEN position removes stale air from the
room and exhausts it to the outside. Fresh air is
drawn into the room through your home's
normal air passages.
• The OPEN or CLOSE position can be used with
any fan selection.
!
CLOSE,-LVENT-LOPEN
FIG. 12
-10-