en - Trouble-shooting
42
Fault
Reason
Does not
No power
switch
(green LED does not light up)
Electronic defect
Contacts welded together (after
short-circuit)
Measuring transmitter defective
Switches
Incorrect setting of change-over
incorrectly
switch for limit signal in FTW325
Permanent
Interrupt or short-circuit line to
alarm signal
measuring transmitter
Measuring transmitter electronics
defective
Nivotester defective
Remedy
Check power
Replace FTW325
Replace FTW325;
connect a fuse into contactor circuit
Replace measuring transmitter
Correctly set change-over switch
behind front panel
Check line
Replace measuring transmitter
electronics
Replace FTW325