Siemens simovert masterdrives Instrucciones De Servicio página 297

Motion control convertidores de frequencia (ca-ca) forma con. en chasis
Ocultar thumbs Ver también para simovert masterdrives:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

08.2008
NOTE
Rating plate
Date of manufacture
Siemens AG
6SE7087-8JK50
SIMOVERT MASTERDRIVES
The derating of the permissible rated current for installation altitudes of
over 1000 m and at ambient temperatures below 40 °C is calculated as
follows:
Total derating = Derating
K = K
x K
1
2
It must be borne in mind that total derating must not be greater than 1!
Example:
Altitude: 3000 m
Ambient temperature: 35 °C
⇒ Total derating = 0.845 x 1.125 = 0.95
Rating plate
Fig. 11-2
The date of manufacture can be derived as follows:
Character
Year of manufacture:
U
V
W
X
Table 11-2
Assignment of characters to the month and year of manufacture
Operating Instructions
x Derating
altitude
ambient temperature
Character
2006
1 to 9
2007
O
2008
N
2009
D
Technical Data
K
= 0.845
1
K
= 1.125
2
Unit designation
List of unit options
Year of manufacture
Month of manufacture
Month of manufacture
January to September
October
November
December
11-3

Hide quick links:

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Se7087-8jk5

Tabla de contenido