Features
1
Primary Input Cord
The cord is permanently attached to the PDU and has a NEMA L5-30P
(PDUMH30AT & PDUMH30ATNET) or NEMA L6-30P (PDUMH30HVAT &
PDUMH30HVATNET) twist-lock plug.
2
Secondary Input Cord
The cord is permanently attached to the PDU and has a NEMA L5-30P
(PDUMH30AT & PDUMH30ATNET) or NEMA L6-30P (PDUMH30HVAT &
PDUMH30HVATNET) twist-lock plug.
3
(PDUMH30ATNET, PDUMH30HVATNET) Switched Outlets: During normal
operation, the outlets distribute AC power to connected equipment. The NEMA
5-15/20R, L5-30R, IEC-320-C13, IEC-320-C19 and L6-30R outlets may be
switched On and Off via software control. When an outlet is live, the associated
LED illuminates.
(PDUMH30AT, PDUMH30HVAT) Unswitched Outlets: The NEMA 5-15/20R,
L5-30R, IEC-320-C13, IEC-320-C19 and L6-30R outlets receive power from
either input source, but are not individually switchable.
IEC-320-C13 Outlets
(PDUMH30HVAT &
PDUMH30HVATNET)
10A (208V)
IEC-320-C19 Outlets
(PDUMH30HVAT &
PDUMH30HVATNET)
16A (208V)
NEMA 5-15/20R
Outlets (PDUMH30AT
& PDUMH30ATNET)
20A (120V)
4
Factory Port: This port is reserved for configuration by factory authorized
personnel only. Do not connect anything to this port.
5
Digital Load Meter (Ammeter): The electrical current drawn by connected
equipment is displayed on the digital load meter in amperes. There are four
display options: the load for the twist-lock outlet (L5-30R or L6-30R, depending
on model), the total load for Bank 1 outlets, the total load for Bank 2 outlets
and the total load for the PDU. Press and hold the switch to display the IP
Address of the SNMP Card in the PDU. Note: Press the "Meter Select" button to
cycle through display options.
201008118 93-3040.indb 7
continued
NEMA L5-30R Outlet
(PDUMH30AT &
PDUMH30ATNET)
30A (120V)
NEMA L6-30R Outlet
(PDUMH30HVAT &
PDUMH30HVATNET)
30A (208V)
7