Installation notes 9410-U9
The module must be installed in a tool-secured enclosure suitable for the application in accordance with the
National Electrical Code (ANSI/NFPA 70) for installation in the United States, the Canadian Electrical Code for
installations in Canada, or other local codes, as applicable.
Install in pollution degree 2, overvoltage category II in accordance with IEC 60664-1.
Use minimum 75 ºC copper conductors with wire size AWG: (26-14)
There are no serviceable parts in the equipment and no component substitution is permitted
Warning: To prevent ignition of the explosive atmospheres, disconnect power before servicing and do not
separate connectors, install or remove modules from Power Rail when energized and an explosive gas
mixture is present.
Avertissement : Pour éviter l'inflammation d'atmosphères explosibles, déconnectez l'alimentation avant les
opérations d'entretien. Ne montez pas ou n'enlevez pas les connecteurs quand le module est sous tension et
en présence d'un mélange de gaz. Ne montez pas ou n'enlevez pas les modules du rail d'alimentation en
présence d'un mélange de gaz..
The 9410-U9 must be supplied from a Power Source with Double or Reinforced insulation to Mains.
Non Hazardous Area or Zone 2
T4: -20 ºC <Ta < +60ºC
91 92 93 94 95
Status
24 V
GND
Revision date:
2019-11-18
22
34
Backup -
33
Backup +
32
Supply +
31
Supply -
14
13
NC
12
COM
11
NO
9410
Power
Rail
Version Revision
V1 R0
9410 - Versión del producto 9410-001
Terminal 34-33
Backup: 21,6 VDC – 26,4VDC / 4ADC
Terminal 31-32
Supply: 21,6 VDC – 26,4VDC / 4ADC
Terminal 11, 12, 13
Power Rail Status Relay
Unclassified installation
250VAC, 2A, 500VA / 30VDC, 2A, 60W
Zone 2 installation:
32VAC, 2A, 64VA / 30VDC, 2A, 60W
Prepared by:
PB
9410QU01
Page:
2/3