Maintenance; Specifications; Fractional Efficiency - Honeywell Home F300 Serie Guía De Instalación Profesional

Limpiador de aire electrónico
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Check Air Cleaner Operation
With all components in place, turn on air cleaner switch and energize system blower. Check following
points of operation:
1. The neon light next to the On-Off switch is on. The neon light shows that the air cleaner is energized and
the high voltage power supply is working correctly.
2. Turn off the system blower. The neon light should go off after a few seconds.
3. Turn on the system blower. With the air cleaner energized, push the test button. A snapping sound
indicates that the collector voltage is present on the cell.
4. With a multispeed blower, repeat steps 1 through 3 for each fan speed.

Maintenance

The air cleaner must be cleaned when pressure drop across the air cleaner reaches 0.5 in. w.c. (0.1 kPa), or
at least annually. If the air cleaner is installed downstream from an atomizing humidifier or if the installation
includes both heating and cooling, more frequent replacement may be necessary. Clogged prefilters must be
cleaned promptly to avoid restricting airflow and reducing efficiency of the heatingcooling system. Record
the maintenance date in the space provided on the Electronic Air Cleaner Wash Reminder and Postfilter
Replacement Schedule.

Specifications

The specifications in this publication do not include normal manufacturing tolerances; therefore, an
individual unit may not exactly match the listed specifications. This product is tested and calibrated
under closely controlled conditions, and some minor differences in performance can be expected if those
conditions are changed.

Fractional Efficiency

Efficiency Ratings: Efficiency ratings are based on American Society of Heating, Refrigerating and Air
Conditioning Engineers Standard 52.2-1999. Efficiency ranges are defined for small particles, E1 =.3 to 1.0
micron; medium particles, E2 = 1.0 to 3.0 microns; and large particles, E3 = 3.0 to 10.0 microns.
14
Table 5. Fractional Efficiency With and Without Postfilter.
With Postfilter
E1 = Up to 81% at 492 fpm.
E2 = Up to 93% at 492 fpm.
E3 = Up to 99% at 492 fpm.
Without Postfilter
E1 = Up to 73% at 492 fpm.
E2 = Up to 88% at 492 fpm.
E3 = Up to 95% at 492 fpm.
F300 Electronic Air Cleaner 68-0240EFS—01