Radio Powr SavrT Occupancy/Vacancy Ceiling Sensor
(LRFX-OCR2B-P, LRFX-OCRB-P, LRF2-VCR2B-P)
To associate the sensor with compatible Lutron products (except GRAFIK
EyeR QS Wireless Control Units), follow the installation guide included with
the product, with the exceptions noted below:
1. During sensor set-up: Skip the step to press and hold the " " button
on the front of the sensor for approximately 6 seconds.
2. I nstead, turn on the laser and pass the beam over the hole in the
sensor. The sensor's lens LED will flash rapidly, then blink once per
second.
3. O nce the sensor is flashing once per second, pass the beam of
the laser over the hole in the sensor again within 10 seconds.
The sensor's lens LED will flash rapidly. For expected response
upon completion of association, refer to your specific product
documentation.
Note: If the laser is not passed over the sensor hole again within the
10-second window, the unit reverts to normal operation.
4. T he sensor automatically goes into Test Mode at this point. When
activated by the green laser, Test Mode lasts for 5 minutes.
Note: in this Test Mode the receiving device will respond to the
occupancy state changes and the occupancy timeout is 20 seconds.
Radio Powr SavrT Occupancy/Vacancy Wall Sensor
(LRFX-OWLB-P, LRFX-OKLB-P, LRFX-OHLB-P, LRF2-VWLB-P, LRF2-VKLB-P, LRF2-VHLB-P)
To associate the sensor with compatible Lutron products (except GRAFIK
EyeR QS Wireless Control Units), follow the installation guide included with
the product, with the exceptions noted below:
1. During sensor set-up: Skip the step to press and hold the " " button
on the front of the sensor for approximately 6 seconds.
2. I nstead, turn on the laser and pass the beam over the hole in the
sensor. The sensor's lens LED will flash rapidly, then blink once per
second.
3. O nce the sensor is flashing once per second, pass the beam of
the laser over the hole in the sensor again within 10 seconds.
The sensor's lens LED will flash rapidly. For expected response
upon completion of association, refer to your specific product
documentation.
Note: If the laser is not passed over the sensor hole again within the
10-second window, the unit reverts to normal operation.
4. T he sensor automatically goes into Test Mode at this point. When
activated by the green laser, Test Mode lasts for 5 minutes.
Note: in this Test Mode the receiving device will respond to the
occupancy state changes and the occupancy timeout is 20 seconds.
Application Note #407
2
Hole in sensor
Hole in sensor
www.lutron.com