Hidraulic circuit for WPH and WPV units and their components:
-
Inside hidraulic circuit and its components, sheet heat exchanger is the most delicate part
affected, and as a result should follow these guidelines at least
-
The water filter must be installed and should contain inside it a mesh to retain particles of diameter
less than 0,5- Ø >0,5mm
-
Both filter and flow switch maintenance must be made within a few periods in which they can
avoid lock dressings
-
Should be respect the indication of water inlet or outlet of unit and install if it derives from a by-
pass valve
-
In case of working with open circuits, which the water quality is not correct and is noted down in
the table, is recommended install a secondary exchanger to avoid its deterioration.
Table water's quality:
Contents in water
Suspended solids
Conductivity
NH
3
Chlorides
Iron
Carbonic Acids
PH
Sulphates
Langelier
05.16 Ref. 200346 Rev. 106
Concentration to mg/l
Changeable
< 500 µs/cm
> 500 µs/cm
Between 2 and 20
< 300
> 300
< 10
> 10
Between 20 and 50
Between 6 and 9
Between 70 and 300
Between -0,5 and +0,5
Superior Value
Can erode the material
Can not appreciate the
afectation
Not recommended
-
Corrosive capacity
Can not appreciate the
afectation
-
Corrosive capacity
Corrosive capacity
Can not appreciate the
afectation
Water with tendency to
create incrustation
Inferior Value
Can not appreciate the
afectation
-
Not recommended
Can not appreciate the
afectation
Can not appreciate the
afectation
-
-
Corrosive capacity
Not recommended
Can not appreciate the
afectation
Corrosive capacity
Water with tendency to
corrosive
25