Los parámetros de "Query Mode, Get Mode", índice 0x80A0, ID servicio 0x03
Byte
Parámetros
0
Blocktype high
1
Blocktype low
2
BlockLength high
3
BlockLength low
4
BlockVersion high
5
BlockVersion low
6
Service Request ID
7
Request Reference
8
Modifier/Status
9
Data Structure ID RQ/RS
10
Parámetros
11
12 ... 15
16 ... 19
20 ... 23
24 ... 27
28 ... 31
32 ... 35
36 ... 39
40 ... 43
Módulo de interfaz IM151-3 PN FO (6ES7151-3BB23-0AB0)
Manual de producto, 08/2010, A5E01062518-04
Lectura
0x08
0x00
0x00
0x08
0x01
0x00
0x03
0x01 ... 0xFF
0x02
0x01
0x01
padding byte
Funciones
3.4 PROFIenergy
Escritura
0x08
0x01
0x00
0x28
0x01
0x00
0x03
0xFF ... 0x01
0x01
0x02
0x01
PE_Mode_Attributes = 0
Time_min_Pause
0x00002710
Time_to_Pause 0x00002710
Time_to_Operate
0x00002710
Time_min_Length_of_stay
0x00000000
Time_max_Length_of_stay
0xFFFFFFFF
Mode_Power_Consumption
= 0
Energy_Consumption_to_pa
use = 0
Energy_Consumption_to_op
erate = 0
39