I2t for blowout: 800A2s
dV/dt critical with output deactivated:
1000V/µs
GTS 40 (SCR version)
Rated current: 40 A@40°C in
continuous service
Non-repetitive overcurrent t=20 ms:
400A
I2t for blowout: 800A2s
dV/dt critical with output deactivated:
1000 V/µs
GTS 50 (SCR version)
Rated current: 50 A@ 40°C in
continuous service
Non-repetitive overcurrent t=20 ms:
1300A
I2t for blowout: 11200A2s
dV/dt critical with output deactivated:
1000V/µs
GTS 60 (SCR version)
Rated current: 60 A@ 40°C in
continuous service
Non-repetitive overcurrent t=20 ms:
1300A
I2t for blowout: 11200A2s
dV/dt critical with output deactivated:
1000V/µs
GTS 90 (SCR version)
Rated current: 90A@ 40°C in
continuous service
Non-repetitive overcurrent t=20 ms:
1700A
I2t for blowout: 25300A2s
dV/dt critical with output deactivated:
1000V/µs
GTS 120 (SCR version)
Rated current: 120A@ 40°C in
continuous service (complete with fan
and standard thermostat)
Non-repetitive overcurrent t=20 ms:
1700A
I2t for blowout: 25300A2s
dV/dt critical with output deactivated:
1000V/µS
Isolation
Rated isolation voltage
input/output:
2500VAC rms TRIAC version
4000VAC rms SCR version
Ambient conditions
• Working temperature:
0 to 80°C (according to
dissipation curves)
• Max. relative humidity:
50% at 40°C
• Max. installation altitude:
2000m asl
• Pollution level: 3
• Storage temperature: -20..+85°C
Installation notes
Use the high-speed fuse specified
in the catalog according to the
connection example given.
For maximum reliability, it is essential
to install the device correctly in the
panel in order to have adequate heat
exchange between the sink and the
surrounding air by natural
convection.
Install the device vertically (max. 10°
inclination to vertical axis)
• Vertical distance between a device
and panel wall >100mm
• Horizontal distance between a
device and panel wall: at least 20mm
• Vertical distance between one
device and another: at least 300mm.
• Horizontal distance between one
device and another: at least 20mm.
Make sure that the cable raceways
do not reduce such distances; if so,
install the groups cantilevered to the
panel so that air can flow
vertically on the heat sink
without obstructions.
Limits of use
• dissipation of thermal power of
device with restrictions on
temperature of installation site.
• requires exchange with outside air
or an air conditioner to transfer
dissipated power outside the panel.
• installation restrictions (distances
between devices to guarantee
dissipation by natural convection)
• max. voltage limits and derivative
of transients in line, for which the
solid state unit has internal protection
devices (depending on model).
• presence of dispersion current
< 3mA for SCR version GTSs
< 4mA for Triac version GTSs.
(max. value with rated voltage
and junction temperature of 125°C).