Technical Data; Commissioning The Device; Operations Prior To Installation - Madas FRG/2MBCL-Z Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2.0 - TECHNICAL DATA

• Use
• Ambient temperature
• Max operating pressure
• Safety lock closing time
• Class
• Overpressure shut off accuracy unit
• Closing pressure class
• Relief valve
• Connecting the vent
• Mechanical strength
• Rp threaded connections
• NPT Threaded connections
• Flanged connections that can couple with PN 16 flanges : on request DN 25 with swivel flanges
• Standard filter element
• In compliance with
2.1 - MODEL IDENTIFICATION (for configurations see pages 44 - 49)
FRG/2MBCL (Z-F-R-M): Pressure filter regulator - Compact version (up to 25 m
FRG/2MBL (Z-F-R-M): Pressure filter regulator - Standard version
Z: Connections in line
F: Connections at 90° IN G 1/2
R: Connections at 90° OUT G 3/4
M: Connections at "U" IN G 1/2 - OUT G 3/4

3.0 - COMMISSIONING THE DEVICE

3.1 - OPERATIONS PRIOR TO INSTALLATION

• It is necessary to close the gas upstream of the device prior to installation;
• Make sure that the line pressure DOES NOT EXCEED the maximum pressure declared on the product label;
• Protective caps (if any) must be removed prior to installation;
• The pipes and inside of the device must be clear of any foreign bodies;
• IMPORTANT:
• to avoid possible pumping and/or disturbances in the gas flow, a straight pipe section equal to at least 5 DN must be
installed (downstream of the regulator);
• install manual gas closing devices (e.g. ball valves) upstream and downstream of the regulator to protect it from any
pipe leak test;
• do consider that if the regulator is equipped with a relief valve, the latter is suitable for small quantities of gas to be
discharged and CANNOT replace the relief valve installed separately as a specific device;
FRG/2MBCL(Z-F-R-M) - FRG/2MBL(Z-F-R-M)
: non-aggressive gases of the three families (dry gases)
: -20 - +60°C
: 0.5 bar
: < 1 s
: A=(P2 ± 15%)
: AG=10
: SG=30
: tested according to the indications in EN 334
: G 1/4
: Group 2 (according to EN 13611)
: (DN 15 - DN 20 - DN 25) according to EN 10226
: on request
: filtering
50µm
: ATEX Directive 2014/34/EU
/h)
3
12
Madas Technical Manual - 4|4.2a - REV. 0 of 1
Apr 2019
st

Publicidad