IMPORTANT:
Provide each unit with a DC power supply from a 5V through 30V (at 10C to 40C) or 7V through 30V (at -30C to
40C)
as applicable circuit used for emergency lighting.
WARNING:
During installation of remotes, input wires from main unit to remote units must NOT be connected to each other
or connected to ground. Failure to due so will lead to failure of the main unit.
NOTE: The maximum mounting height with tilt and swivel lamp heads are shown below to meet the minimum illumination
requirements of NFPA 101 (Current Life Safety Code).
ELMRE LP220L SGL/T
Junction box mounting:
1
-Some details shown below may vary-
A. Use code-approved connectors to connect input leads inside
J-box [See label on wire pair for positive and negative
polarity colors].
B. On the mounting plate, open the desired keyhole junction-
box knockouts.
C. Route input connector through center hole in mounting plate.
D. Taking care not to pinch wires or connectors dressed inside
junction box, secure mounting plate to junction box screws.
NOTE: to ensure proper engagement of the mounting plate
latches to the housing, DO NOT OVER-TIGHTEN THE
SCREWS.
Housing attachment to mounting plate:
2
A. Plug the input connector to the receptacle on the lamp
driver board.
B. Ensure that wires are routed to avoid interference with
other components, and push housing straight onto mounting
plate, making certain both latches are fully engaged.
INSTALLATION and WIRING
8.7/11.8 ft
ELMRE SP640L SGL/T
LIFE SAFETY SOLUTIONS
TEL: 800-334-8694
24.4/31.9 ft
ELMRE SP1100L SGL/T
Push housing straight onto mounting plate
www.lithonia.com
30.8/43.4 ft
Junction boxes accommodated:
4" Square
4" Octagon
3-1/2" Round or Octagon
Single Gang Box
Part # 912-00028-001
Rev. C, 05/2020