Cable Sizes

AC Input
UPS Model
Gauge
50mm
2
S3MT-
Max.
60K480V
50mm
x2
2
35mm
2
S3MT-
Max.
60K600V
50mm
x2
2
70mm
x2
2
S3MT-
Max.
100K480V
120mm
x2
2
50mm
2
S3MT-
Max.
100K600V
70mm
x2
2
Cable Sizes (THHW wiring at 75°C)
AC Output
Torque
Gauge
50mm
2
25N•m
Max.
50mm
x2
2
50mm
2
25N•m
Max.
50mm
x2
2
70mm
x2
2
50N•m
Max.
95mm
x2
2
70mm
x2
2
50N•m
Max.
95mm
x2
2
Neutral
Torque
Gauge
70mm
x2
2
25N•m
Max.
70mm
x2
2
70mm
x2
2
25N•m
Max.
70mm
x2
2
120mm
x2
2
50N•m
Max.
120mm
x2
2
120mm
x2
2
50N•m
Max.
120mm
x2
2
12
Grounding
Torque
Gauge
50mm
2
25N•m
Max.
50mm
x2
2
50mm
2
25N•m
Max.
50mm
x2
2
95mm
2
50N•m
Max.
120mm
2
95mm
2
50N•m
Max.
120mm
2
Lug
Torque
25N•m
M8
25N•m
M8
50N•m
M10
50N•m
M10