TECHNICAL DATA
KNX Supply Voltage
Power Consumption
Sampling rate
Programming by
KNX Topology
Commissioning
Dimensions
Weight
Working Temperature
Storage Temperature
Degree of Protection
According to the Directives
According to the Standards
CHARACTERISTICS
1-channel button glass touchless (contactless) switches which provide full control to the
user over the lighting, the blinds and, in turn, the ability to memorize scenes to generate
desired atmospheres at any time, without the need to physically touch any contact
surface.
Two different designs:
D
· PU KNT PR1: Black glass and perimetral frame in copper color.
· PU KNT PR2: White glass and perimetral frame in chrome color.
Incorporate temperature sensor.
They have 2 RGB LEDs (C), whose behavior can be parameterized via ETS.
The sensitivity of the proximity sensor (D) can also be adjusted via ETS
Possibility of press confirmation by sounds.
KNX Bus Coupling Unit (BCU) integrated.
Commissioning by ETS5 or later versions.
DESCRIPTION
The pushbuttons consists of different elements (Fig. 1 & 2):
· A: KNX bus connector.
· B: Programming LED and button.
· C: RGB LEDs.
· D: Proximity sensor.
MOUNTING AND INSTALLATION
Follow the steps below to install the pushbutton (Fig. 3):
1 - Place the plastic base in the mechanism box using the two screws included in the
packaging.
2 - Connect the bus line to the KNX connector (A) respecting the polarity.
3 - Press the push button on the plastic base, pushing it until it is perfectly tied.
DIMENSIONS (Fig. 4)
COMMISSIONING
NOTE: Download application software: www.dinuy.com
1 - Assign the physical address and set parameters with the ETS.
2 - Press the programming key and program (B) of the pushbutton.
3 - After a sucessful programming the red LEDs (B) will be turned off.
14mm 13mm
30mm
WARNING!:
Installation and assembly of electrical equipment must be carried out only by a
skilled person!
Connect only to suitable supply voltage (KNX bus voltage)!
Installation and assembly of electrical equipment must be in accordance with
national building, electrical and safety codes!
GB
21 ~ 32V
DC
<4mA
75msec
ETS5
TP1
System Mode
90 x 90 x 14mm
165g
-5ºC ~ +45ºC
-30ºC ~ +70ºC
IP20 according to EN60529
Security 2014/35/EU
EMC 2014/30/EU
KNX Standard 2.0
EN60669-1, 2-1 & 2-3