15. TECHNICAL DATA

Housing: self extinguishing ABS.
Case: XR30CX frontal 32x74 mm; depth 60mm;
Mounting: XR30CX panel mounting in a 71x29mm panel cut-out
Protection: IP20; Frontal protection: XR30CX IP65
Connections: Screw terminal block  2,5 mm
Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac 10%,
50/60Hz, 110Vac 10%, 50/60Hz
Power absorption: 3VA max
Display: 3 digits, red LED, 14,2 mm high; Inputs: Up to 4 NTC or PTC probes.
Digital input: free voltage contact
Relay outputs: compressor SPST 8(3) A, 250Vac; or 20(8)A 250Vac
AUX: SPDT 8(3) A, 250Vac
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B; Pollution grade: 2;Software class: A.;
Rated impulsive voltage: 2500V; Overvoltage Category: II
Operating temperature: 0÷60 °C;Storage temperature: -30÷85 °C.
Relative humidity: 2085% (no condensing)
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);
PTC probe: -50÷150°C (-58÷302°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable);
Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit.

16. CONNECTIONS

The X-REP output excludes the TTL output.. It's present in the following codes:
XR30CX- xx2xx, XR30CX –xx3xx;
16.1 XR30CX – 8A COMPRESSOR
8(3)A250V
8(3)A250V
1 2
3 4
Light/
N.C.
Alarm
Comp
Line
9-40Vdc supply: connect to the terminals 7 and 8.
12Vac/dc supply: connect to the terminals 7 and 8.
24Vac/dc supply: connect to the terminals 7 and 8.
120Vac supply: connect to the terminals 7 and 8.
16.2 XR30CX – 20A COMPRESSOR
8(3)A250V
20(8)A250V
1 2
3 4
Light/
N.C.
Alarm
Comp
Line
9-40Vdc supply: connect to the terminals 7 and 8.
12Vac/dc supply: connect to the terminals 7 and 8.
24Vac/dc supply: connect to the terminals 7 and 8.
120Vac supply: connect to the terminals 7 and 8.

17. DEFAULT SETTING VALUES

Label
Name
Set Set point
Hy Differential
LS Minimum set point
US Maximum set point
Ot
Thermostat probe calibration
P3P Third probe presence
O3 Third probe calibration
P4P Fourth probe presence
O4 Fourth probe calibration
OdS Outputs delay at start up
AC Anti-short cycle delay
CCt Continuos cycle duration
CCS Set point for continuous cycle
COn Compressor ON time with faulty
probe
COF Compressor OFF time with faulty
probe
CH Kind of action
CF Temperature measurement unit
rES Resolution
1592020030 XR30CX GB m&M r1.1 27.03.2015
wiring.
2
9 10 11 12
5
6
7
8
Hot Key/IV probe
TTL or X-REP output
9 10 11 12
5
6
7
8
Hot Key/IV probe
TTL or X-REP output
Range
°C/°F
LS÷US
0,125.5°C/ 1 255°F
-50°CSET/-58°FSET
-50.0
SET110°C/ SET  230°F
-1212°C /-120120°F
n=not present; Y=pres.
-1212°C /-120120°F
n=not present; Y=pres.
-1212°C /-120120°F
0÷255 min
0  50 min
0.0÷24.0h
(-55.0÷150,0°C) (-67÷302°F)
0  255 min
0  255 min
CL=cooling; Ht= heating
°C  °F
in=integer; dE= dec.point
dLy Display temperature delay
IdF Interval between defrost cycles
MdF (Maximum) length for defrost
dFd Displaying during defrost
dAd MAX display delay after defrost
ALc Temperat. alarms configuration
ALU MAXIMUM temperature alarm
ALL Minimum temperature alarm
AFH Differential for temperat. alarm
recovery
ALd Temperature alarm delay
dAo Delay of temperature alarm at start
up
AP2 Probe for temperat. alarm of
condenser
AL2 Condenser for low temperat. alarm
AU2 Condenser for high temperat. alarm (-55 ÷ 150°C) (-67÷ 302°F)
Differ. for condenser temp. alar.
AH2
recovery
Condenser
Ad2
delay
Delay of cond. temper. alarm at
dA2
start up
Compr. off for condenser low
bLL
temperature alarm
Compr. off for condenser high
AC2
temperature alarm
tbA Alarm relay disabling
oA1 2
nd
AoP Alarm relay polarity (oA1=ALr)
i1P Digital input polarity
i1F Digital input configuration
did Digital input alarm delay
nPS Number of activation of pressure
switch
odc Compress status when open door
rrd Regulation restart with door open
alarm
HES Differential for Energy Saving
Adr Serial address
PbC Kind of probe
onF on/off key enabling
dP1 Room probe display
dP3 Third probe display
dP4 Fourth probe display
rSE Real set point value
rEL Software release
Ptb Map code
3.0
- - -
2.0
Pr1
Pr2
110
Pr2
0.0
Pr1
n
Pr2
0
Pr2
n
Pr2
0
Pr2
0
Pr2
1
Pr1
0.0
Pr2
3
Pr2
15
Pr2
30
Pr2
cL
Pr1
°C
Pr2
dE
Pr1
XR30CX
0 ÷ 20.0 min (10 sec.)
Set110.0°C; Set÷230°F
-50.0°CSet/ -58°FSet
(0,1°C÷25,5°C) (1°F÷45°F)
nP; P1; P2; P3; P4
(-55 ÷ 150°C) (-67÷ 302°F)
[0,1°C ÷ 25,5°C] [1°F ÷
temperature
alarm
0 ÷ 254 (min.) , 255=nU
relay configuration
ALr = alarm; dEF = do not
select it; Lig =Light; AUS
=AUX; onF=always on; Fan=
do not select it; db = do not
select it; dF2 = do not select it
oP=opening;CL=closing
EAL, bAL, PAL, dor; dEF; Htr,
AUS
(-30°C÷30°C) (-54°F÷54°F)
0
Pr2
1  120 ore
8
Pr1
0  255 min
20
Pr1
rt, it, SEt, DEF
it
Pr2
0 ÷ 255 min
30
Pr2
rE= related to set;
Ab
Pr2
Ab = absolute
110
Pr1
-50.0
Pr1
1
Pr2
0  255 min
15
Pr2
0  23h e 50'
1.3
Pr2
P4
Pr2
-40
Pr2
110
Pr2
5
Pr2
45°F]
15
Pr2
1,3
Pr2
0.0 ÷ 23h 50'
n
Pr2
n(0) - Y(1)
n
Pr2
n(0) - Y(1)
n=no; y=yes
y
Pr2
Lig
Pr2
oP; cL
cL
Pr2
cL
Pr1
dor
Pr1
0÷255min
15
Pr1
0 ÷15
15
Pr2
no; Fan; CPr; F_C
no
Pr2
n – Y
y
Pr2
0
Pr2
0÷247
1
Pr2
Ptc; ntc
ntc
Pr1
nu, oFF; ES
nu
Pr2
--
--
Pr2
--
--
Pr1
--
--
Pr1
actual set
--
Pr2
--
--
Pr2
--
--
Pr2
4/4

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido