Special Conditions Of Use (X Conditions) - WIKA TIF11-I Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4. Specifications / 5. Special conditions of use ...
4.2 Model TIF11-F
The model TIF11-F field transmitter consists of a case with ignition
protection type "flameproof enclosure".
EN
Within the case can be installed suitable temperature transmitters with
U
= DC 30 V and P
max

5. Special conditions of use (X conditions)

5.1 Model TIF11-I
Installation in areas requiring EPL Ga or EPL Gb equipment
Electronic assemblies of field transmitter model TIF11-I shall be
mounted in an enclosure, suitable for installation in EPL Ga or EPL Gb
area respectively, wherein electrostatic charge effects are excluded.
The enclosure shall provide as a minimum degree of protection IP20
according to EN 60529.
Wiring inside this housing shall satisfy the conditions of clause 6.3.12
and 7.6.e of EN 60079-11:2012.
Terminals or connectors for the intrinsically safe circuits shall be
arranged according to clause 6.2.1 or 6.2.2 of EN 60079-11:2012
respectively.
Installation in areas requiring EPL Da or EPL Db equipment
Electronic assemblies of field transmitter model TIF11-I shall be
mounted in an enclosure, suitable for installation in EPL Da or EPL Db
area respectively, wherein electrostatic charge effects are excluded.
The enclosure shall provide as a minimum degree of protection IP5x
(Group IIIB application) or IP6x (Group IIIC application) according to
EN 60529.
Wiring inside this housing shall satisfy the conditions of clause 6.3.12
and 7.6.e of EN 60079-11:2012.
Terminals or connectors for the intrinsically safe circuits shall be
arranged according to clause 6.2.1 or 6.2.2 of EN 60079-11:2012
respectively.
5.2 Model TIF11-F
No special conditions of use
8
= 2 W.
max
WIKA additional information, models TIF11-I (Ex i), TIF11-F (Ex d)

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Tif11-f

Tabla de contenido