Elkron MC500 Manual De Instrucciones página 5

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

ADDRESSING
The
address
(1-128)
software and stored in non-volatile memory.
The module can be addressed, in manual or
automatic mode by the control panel. When the
JP1 jumper is removed, the module is powered
off. This feature is useful during the walk-
addressing procedure.
For further details see the FAP control panel's
programming manual.
CONNECTIONS
Digital detection circuit:
A shielded cable must be used; connect the
shield of the cable to the ground of the control
panel only (if the detection circuit is in loop
mode, connect one end only of the shield).
Check the electrical integrity of the shield in the
whole circuit.
The section of leads can vary according to the
length of the detection circuit.
A lead section of 1,5 mm
Do not use a cable that exceeds these limits:
Maximum resistance = 100 Ω
Maximum capacitance = 2 µF
Conventional detection circuit:
A shielded cable must be used; connect the
shield only to the terminal block present on the
module. Leave the other end of the circuit
disconnected. Check the electrical integrity of
the shield in the whole circuit.
Each detector placed on the conventional
detection circuit must be connected in series
and the end of line resistor must be connected
to the last device, so in case of detector
removal, a fault indication is generated by the
control panel.
Do not use a cable that exceeds 50 Ω of
resistance.
Siren output:
Use a bipolar cable with proper section
according to the current required by the siren
and the distance between the module and the
siren. The end of line resistor must be placed
near the siren. If the siren output is not used, the
end of line resistor must be connected between
the positive and negative siren output terminal
boards of the module.
is
programmed
via
2
is advised.
Power supply:
Use a bipolar cable with proper section
according to the current required by the
module/siren and the distance between the
power supply and the module.
Connection diagram
The MC500 module is only to be used with
ELKRON FAP series control panels.
TESTING
(
trained personnel
Before testing, notify to competent authority that
the system is temporarily out of service due to
maintenance operations.
To test the module to act on the detector placed
on the line of conventional detection, as
prescribed by the manufacturer of the detector
itself. Occur in the control panel alarm condition.
At the end of testing operations, restore the
system to normal operation and notify the status
to the competent Authorities
5/12
)

Publicidad

Tabla de contenido
loading

Tabla de contenido