Mounting

3.1 Installation

1. The digital display shall not be installed near to con-
tactors or motor starters.
2. We recommend the use of wire end ferrules in order
to avoid short-circuits between adjacent terminals.
3. In order to keep the interferences at the measuring
input as low as possible, the signal and power sup-
ply wires must be routed separately.
4. Use shieded cables for all signal/probe wirings and
avoid routing the signal/probe wirings parallel to
each other. The shield shall only be grounded at one
point in order to avoid ground loops.
3.2

Electrical connection

3.2.1 Pt100/Ni100 resistance thermometers
2-wire resistance thermometer
1 2 3 4 5 6 7
4-wire resistance thermometer
1 2 3 4 5 6 7
3.2.2 Supply voltage and Latch input
connection
1 2 3 4 5 6 7
3
14
ϑ
ϑ
2
1
Important note:
Before carrying out any installation or maintenance
work, make sure that the power supply of the digital
display is switched off.
3-wire resistance thermometer
1 2 3 4 5 6 7
3
Latch input
2
0 V DC (GND)
1
10 ... 30 V DC
ϑ