Press "
" and "
At this moment, first 2 digits of the nixie tube "
is specific parameters. Press "
When enter the parameter query, it will quit automatically and return to the main interface. Press "
and "
" simultaneously to quit parameter query manually.
Checking content table (for control panel and wired controller check)
Order
Contents
01
Frequency
Running mode: 0-Power off,1-water pump,2-cooling,3-heating,4-force cooling
02
03
Fan speed: 0-Shutdown,1~7-Fan speed.
04
Total capacity requirements. Capacity before revised(Force cooling displays 5)
05
The revised capacity requirements. (Force cooling displays 5)
06
Cooling/heating temp. setting.
07
T3 temperature value (Outlet temperature of outdoor heat exchanger)
08
T4 temperature value (Outdoor environment temperature)
09
Tp temperature Value (Discharge refrigerant temperature)
10
Tin temp. Value (Inlet water temperature)
11
Tout temp. Value (Outlet water temperature)
12
Tb1 temp. Value (Temperature 1 of heat plate)
13
Tb2 temp. Value (Temperature 2 of heat plate)
T6 temp. Value (Reserved , Cooling fin surface temperature)
14
15
Outdoor unit operation current
16
Power supply voltage AD value
17
Electronic expansion valve opening steps(Step number *8)
18
The last error cord
19
The second error cord
20
The first error cord
17.1.3 Auto-lock (unlock) function
If don't operate the controller in 60s, the keyboard will lock automatically. Press "
simultaneously for 3s to unlock.
17.1.4 Factory Reset
In main interface, long press "
Display panel will display "OFF".
58
" simultaneously for 3s to enter into the interface of parameter query function.
" or "
" for 3s, the unit will close and recovers to factory default mode.
" will display sequence number and the last 2 digits
" to query the relative parameters.