GB/IE
Safety Rules
Please read carefully this Safety Rules before installing or operating the UPS.
We recommend that this manual Safety Rules be kept next to the UPS for future references.
-
Move the UPS in an upright position in its original package to the final destination room.
To lift the cabinets, use a forklift or lifting belts with spreader bars.
-
Check for sufficient floor and elevator loading capacity.
-
Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS.
Contact the nearest Service Centre immediately.
-
WARNING! RISK OF ELECTRICAL SHOCK:
Do not remove covers, there are no user serviceable parts inside.
-
After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltage remains at
the terminals of the electrolytic capacitors.
-
All maintenance and service work should be performed by qualified service personnel.
The UPS contains its own energy source (battery).
-
The field-wiring outlets may be electrically live, even when the UPS is disconnected from the mains.
-
Dangerous voltages may be present during battery operation.
-
The battery must be disconnected during maintenance or service work.
-
This UPS contains potentially hazardous voltages.
-
Be aware that the inverter can restart automatically after the mains voltage is restored.
-
End user must follow applicable regional occupational safety codes/regulations during installation, operation and
equipment maintenance. This may require additional field marking or labeling defining appropriate level of PPE
(Personal Protection Equipment) to reduce the risk of Arc-flash related injuries. Contact our Technical Support for
product specific information.
-
This UPS must be installed and connected only by trained personnel.
-
Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
-
After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are correctly
reattached.
-
This UPS is intended for use in a controlled indoor environment free of conductive contaminants and protected
against animals intrusion.
-
WARNING! HIGH EARTH LEAKAGE CURRENT:
Earth connection is essential before connecting to AC input!
-
Switching OFF the unit does not isolate the UPS from the mains.
-
Do not install the UPS in an excessively humid environment or near water.
-
Avoid spilling liquids on or dropping any foreign object into the UPS.
-
The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 40°C (104°F).
-
Optimal battery life is obtained if the ambient temperature does not exceed 25°C (77°F).
-
It is important that air can move freely around and through the unit. Do not block the air vents.
-
Avoid locations in direct sunlight or near heat sources.
-
Store the UPS in a dry location; storage temperature must be within -25°C (-13°F) to +55°C (131°F).
-
The optimal temperature for Battery storage is 20°C (68°F) to 25°C (77°F) and shall never exceed the range -20°C
(-4°F) to +40°C (104°F).
-
If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time depending on
storage temperature).
-
The battery-voltage is dangerous for person‟s safety.
When replacing the battery, use the same cells number, voltage (V), capacity (Ah).
-
All the battery used, shall be of the same manufacturer and date of production.
-
Proper disposal or recycling of the battery is required.
Refer to your local codes for disposal requirements.
-
Never dispose of battery in a fire: they may explode.
-
Do not open or mutilate battery: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
-
Avoid charging in a sealed container.
-
Never short-circuit the batteries.
When working with batteries, remove watches, rings or other metal objects, and only use insulated tools.
-
In case of air shipment, the cables +/- going to the battery fuses/terminals shall be disconnected and isolated.
Modifications reserved
GE_UPS_USR_XCE_LPS_SGS_STP_XXX_V080.docx
Critical Power
GENERAL
INSTALLATION
STORAGE
BATTERY
English
Page 4/49
UPS Safety Rules