Setting and operating mode of zone 1 and
zone 2 managed with Room Thermostat
- Press the heating circuit operating
mode button (2)
- Turn the knob (5) and select the desired
zone
- Press the OK button (6) to confi rm
- Press the heating circuit operating
mode button (2) to select the desired
operating mode
- Press the OK button (6) to confi rm
NOTE: it is necessary to have a heating
request (TA closed).
Setting and operating mode of zone 3
managed with Room Thermostat
(zone 3 enabled on parameter 5890 set to
"Heat circuit pump HCP Q20" value)
- Press the OK button (6) once
- Press the INFO button (3) until the
"menu list" appears
- Turn the knob (5) and select the
"Installateur" menu
- Press the OK button (6) to confi rm
- Turn the knob (5) and select "heating
circuit P"
- Press the OK button (6) to confi rm
- Turn the knob (5) and select the "1300
operating mode" parameter
- Press the OK button (6) to confi rm
- Turn the knob (5) and select the desired
operating mode
- Press the OK button (6) to confi rm
NOTE:
If zone management is performed via
remote control QAA75, the operating mode
must be set on the remote control itself.