Expansion Board Electric Features; Electronic Probes Features - AERMEC KTU Manual De Instalación, Uso Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

6.2.

EXPANSION BOARD ELECTRIC FEATURES

Power supply:
Terminal board:
CPU:
Activations delay times:
max. transmission speed:
Analogue inputs
Analogue conversion
Number and type
Inputs time constant:
Inputs internal resistance 0...20 mA
!
WARNING:
for the power
supply of any active probes, it is possible
to use the 12 Vdc available on clamp
+Vdc, the maximum current supplied is
100 mA protected against short circuits.
To power the probes 0...5V use +5 Vref
(30 mA max). Like the pCO1 and pCO2
6.3.

ELECTRONIC PROBES FEATURES

Power supply:
Absorption (active outputs)
Work field
Temperature Precision (**):
Humidity (**):
Storage conditions
Working conditions
Temperature sensor
Humidity output signals
Temperature output signals
Terminal board
Container protection rating
Sensitive element protection rating
(*) 100 mV % R.H.: for ASWC112000/ASWC115000 models only.
(*) 200 mV/°C.: for ASWC112000 model only.
18
KTU_5890967_00
28 Vdc +10/-20 % and 24 Vac +10/-15% 50...60 Hz - maximum absorption P= 6 W
with extractable male/female connectors, max. voltage 250 Vac
cable section: min. 0,5 mm2 - max 2.5 mm2
single chip 8 bit; 4.91 MHz
0.5 s
19200 bit/s
A/D converter to 10 bit CPU built-in
4 NTC Carel sensors(-50T90 °C; R/T 10 kΩ at 25 °C), voltage: 0/1 Vdc or 0/5 Vdc,
current: 0...20 mA or 4...20 mA, can be selected via software two at a time (B1, B2 and
B3, B4)
1 s
100 Ω
the 0/1 Vdc signal must be intended
as limited to the restricted range 0-1 V
and is therefore not always compatible
with the standard 10 mV/°C signal
of the Carel probes ( for negative
temperatures and those over 100 °C a
probe alarm can be generated)- For
9/30 Vdc, ±10%
12/24 Vac, -10%, +15%
24 Vac/dc, -10%, +15% for the ASWC112000/ASWC115000 models only
• output in current (maximum absorption with two outputs)
35 mA with 12 Vdc power supply
24 mA with 24 Vdc power supply
50 mA with 12 Vac power supply
24 mA with 24 Vac power supply
• output in voltage (typical absorption with 10 kΩ charge)
10 mA with 12 Vdc power supply
8 mA with 24 Vdc power supply
temperature
humidity
• NTC (res.) range 0T50 °C ±0,25 °C at 25 °C, ±0.5 °C from 0 °C to 50 °C
• NTC (active) range 0T50 °C ±0.4 °C at 25 °C, ±1.2 °C from 0 °C to 50 °C
• PT1000 (active) range -10T70 °C ±0.2 °C at 25 °C, ±0,7 °C from -10 °C to 70 °C
Humidity (**): • range 10/90 % R.H. ±3 % at 25 °C, ±6 % from 10 % U.R. to 90 % U.R.
in the 0T50 °C range
(**) Temporary variations are possible within ±12 % R.H. and ±2 °C, in presence
of electromagnetic fields of 10 V/m.
-20T70 °C; 90 % R.H. not condensing
-10T70 °C or 0T50°C; 90 % R.H. not condensing
NTC (10 kΩ 1 % at 25°C) or PT1000 in Class B
reference range 0/100 % R.H. independently from the range of measurement
voltage 10 mV/% R.H. (charge Rmin = 1 kΩ) (*)
current 4/20 mA (charge Rmax = 100 Ω) 4 mA=0 % R.H.; 20 mA=100 % R.H.
reference range range of measurement
voltage 10 mV/°C (charge Rmin = 1 kΩ) (*)
current 4/20 mA (charge Rmax = 100 Ω) 4 mA=0 °C; 20 mA=50 °C
4 mA=-10 °C, 20 mA=70 °C
NTC res. compatible with CAREL controllers
screw clamps for cables with max. section 1.5 mm2 - min.0,2 mm2
IP30
IP30
signals in temperature, therefore use
4...20 mA or NTC.
-10T70 °C or 0T50 °C depending
on the model
10/90 % R.H. (0T50 °C)