2
Stop:
To stop the X8I press Stop.
The X8I will respond dependant on the setup of item 'CF'
in menu S02:
Pressure regulation control is automatically transferred
back to each compressor. The compressor(s) will continue
to operate using the pressure settings programmed or set
in the individual compressor controller(s).
The X8I will hold each compressor in an offload state.
If the compressor is equipped with a main motor run-on-
time function the compressor will run offload for a period
of time and then stop in to a 'standby' or 'auto restart'
state.
The design of some air compressor control systems
may inhibit automatic transfer of pressure regulation
control to local operation mode. In this instance the
compressor will not continue production of compressed
air – consult the air compressor manual or your air
compressor supplier / specialist for details before
installing the IAX4.
Start:
To start the X8I press Start.
If the Prefill function is enabled, and system pressure is
below the set prefill pressure, the system will enter Prefill
mode for the set Prefill time.
Prefill
To manually skip the Prefill function, press and hold
Start for several seconds.
When Prefill is complete, if applicable, the X8I will enter
normal operating mode.
The X8I will operate in accordance with the parameters
and options set in the active 'Table' .
Tables
Each compressor in the system must be started
(running or in a standby or auto restart condition) before
X8I control of the compressor can be established. The X8I
will not start a compressor that is in a stopped condition.
Power Failure Auto-Restart
the X8I will automatically start, when power is restored
after a disruption or failure, if the X8I was in a 'started'
state when the power disruption or failure occurred.
3
4
The X8I will not automatically restart if the X8I was in
a stopped state when the power disruption or failure
occurred.
Failure Mode
If the X8I experiences a disruption to normal control, or
an X8I shutdown fault occurs, pressure regulation control
is automatically transferred back to each compressor. The
compressor(s) will continue to operate using the pressure
settings programmed or set in the individual compressor
controller(s).
Reset
condition press Reset.
25
If the power failure auto-restart function is enabled
To reset an X8I Alarm (Warning) or Shutdown