TrueZONE ARD, EARD, and ZD
Series Damper Assemblies
For Full Installation Instructions
Visit www.forwardthinking.honeywellhome.com to
download installation instructions and learn more
about TrueZONE products.
INSTALLATION
1. Unpack the damper and install into ductwork.
NOTE: For insulated duct, slide the insulation
under the actuator and tape it to the
actuator's outside flange to seal.
NOTE: In unconditioned spaces, mount the
actuator only on the side or top of the
damper. Mounting on the bottom of the
damper may result in condensation
dripping into the actuator.
2. Set the range stop to the desired position.
Position 0 means fully closed.
NOTE: On ARD/ZD models, range stops pre-
vent full closure. On EARD model,
range stop prevents full open.
Table 1. Approximate ARD/ZD Bleed Rate.
Position
0
1
2
3
3. Wire the actuator. See "Typical Wiring Exam-
ples" on page 2.
a. For 2 wire usage, wire M1 and M6. See Fig. 1.
b. For 3 wire usage, break the plastic tab to
access M4. See Fig. 2.
c. For EARD wiring, use only 2 VENT terminals.
See Fig. 4
Bleed Rate
Closed
16%
30%
50%
INSTALLATION INSTRUCTIONS
33-00079EFS-07