HIGH CURRENT: the current measured from the C.T. exceeds the
110% In. the alarm relay operates in the programmed mode.
LOW CURRENT: the current measured from the C.T. is less than
6%In for 5secs.: if this conditions during more than 2 min.
the regulator switch OFF all the capacitors banks, and the
alarm relay operates in the programmed mode.
UNDER COMPENS: this alarm appears when the PFC equipment
does
not
reach
and the alarm relay operates in the programmed mode.
OVER COMPENS: this alarm appears when the cosφ is Capacitive
for 2 min; the regulator switches OFF all the capacitors
banks and the alarm relay operates in the programmed
mode.
HIGH THD%: the harmonic distortion value is more than the
THERM THD% value set on the PAR SETUP menu; the
regulator switches OFF all the banks and the alarm relay
operates in the programmed mode.
OVER THD%: the harmonic distortion value is over the
instantaneous OVER THD% value set on the PAR SETUP
menu; the regulator switches OFF all the banks and the
alarm relay operates in the programmed mode.
OVER TEMPERATURE: the temperature measured by the probe
(if connected) is over the value set in the PAR SETUP menu
the regulator switches OFF all the banks and the alarm relay
operates in the programmed mode.
MAIN FAILURE: no supply voltage or less then the minimum limit
on the volt signal input gate. The ALARM relay switch-on
end disconnection of all the capacitors banks (alarm
displayed only in BMR8 and 12)
The normal functions resume when the alarm condition ends and
the alarm relay is reset.
MAIN FEATURES
• ABS enclosure of dimensions:
• Voltage supply 380V-415V ( on request 230V)
• Measuring input voltage max 525Vac
• Measuring input current by C.T. xx /5A
• Main current setting range 5A to 10000A
• Voltage/current true RMS measurement
• Current THD% distortion up to 32° harmonic
• Power factor measurement (cosφ)
• Measurement system based on 2 of 4 quadrants
• External voltage transformer settings
• Start ventilation temperature setting (FAN)
• Max. operating temperature for Alarm (OVERTEMP)
• Power factor setting range 0.85 Ind to 0.95 Cap
• Single step reactive power setting (kvar) 0.1 to 6000
• Switching time between steps 5 to 240s ( default 30 )
• Rating voltage capacitors setting 80 to 650V
• Cosφ visualization on fundamental voltage/current measure
• Sensibility on delay time range set
• Max. Continuous THDI set value (THERM THDI%)
• Max. Instant. THDI set value (OVER THERM THDI%)
• THDI% sensibility time delay setting
• Measurements:
True RMS line current and voltage
o
Fundmental current value
o
Harmonic current
o
Power factor based on RMS values
o
Current THDI% value
o
Operating temperature in °C (by probe)
o
MU 03.14 MMM R.4 – COMAR 381011
the
target
cosφ
for
144x144x57mm for BMR 8 and 12
96x96x57mm for BMR 4 and 6
TECHNICAL DATA
Operating voltage:
Operating frequency:
Consumption:
Voltage input:
15min;
Current input:
Power Factor range:
Measures:
LCD Display:
Led:
Switching banks relay:
Alarm output relay:
Output contacts rating:
Interface connectior:
Operating temperature:
External degree protection:
Communication protocol:
WARRANTY
Comar Condensatori s.p.a. guarantees its products for 12 months
from purchase date.
Technical specifications are valid under normal operating conditions
as specified in this document. We do not accept any responsibility
for any misuse of the product and cannot be held liable for indirect
or consequential damages.
IMPORTANT:
Be sure to know the harmonics characteristic of the network
that must be compensated, then ensure the P.F.C. equipment
or capacitors you are using are suitable for the network
characteristics.
REFERENCES
CEE 73/23 e 93/68
CEE 89/336 e 93/68
EN 61000-6-1 – EN 61000-6-2
EN 61000-6-3 – EN 61000-6-4
EN 60335-1
Max. current/voltage measured
o
Voltage, Current, C
16 characters 4 rows backlight
Relay step; MAN/AUT mode;
8A 250V (AC1), max switching
MODBUS RTU – RS232 or RS485
Active, reactive and Apparent Power (only for
o
BMR 8 and 12)
Difference between the operating reactive power
o
and his setting
Weekly power factor value (medium)
o
Active/reactive power measured on 4 qudrants
o
(bassa tensione - low voltage)
(EMC)
380-415 V c.a. + - 10%
50/60 Hz
5VA
maximum 525V
2.5 – 110% Ie
0.85 Ind a 0.95 Cap
osφ, THDI%,
Inductive,Reactive and
IND/CAP; FAN
4 (BMR4) - 6 (BMR6)- 8
(BMR8) – 12 (BMR12)
1 (programmable)
440V
Standard
-20°C + 55°C
IP41 ; optional IP54-IP65
7 / 17