Descargar Imprimir esta página

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 2

Enlaces rápidos

Contactor
Operating Instructions
Read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before
working on this device.
CAUTION
Reliable functioning of the equipment is only ensured with
certified components.
Mounting
For dimension drawings see Fig. I (dimensions in mm)
Fix on a plain surface with two M4 screws - max. tightening torque 3.1 Nm. Always
use plain washers and spring washers. Cover the contactors during installation if
foreign particles, such as swarf, can fall onto them. Install contactors in a housing if
they are exposed to dirt, dust or aggressive atomspheres.
For permissible mounting positions see Fig. II.
Connection
Tighten all terminal screws even if not used.
Permissible conductor cross-sections for main terminals:
With box terminal
According to DIN EN50027
- see Fig. IIIa
Finely stranded with end sleeve (mm
Finely strande without end sleeve (mm
2
Solid, stranded (mm
)
AWG wires, stranded
Stripped length
Tightening torque
1)
The ends of non-stranded cables must be twisted or 18 mm long end sleeves to
DIN 46228 Part 1 must be used.
Crimping tools PZ18 and PZ35 from Weidmuller are recommanded for the end
sleeves.
Before mounting the box terminals (see Fig. IIIb), the arc chute must be removed
(see Fig. VII / 1, 2, 3).
Without box termina
-see Fig. IIIc
1 or 2 conductors can be connected
Finely stranded with terminal pin (mm
2
2)
Stranded with terminal pin (mm
)
Terminal bars
AWG wires, stranded and solid
Terminal screw
Tightening torque
2)
Use cover 3TX7466-0A for oversided cable lugs, for mounting see Fig. IIId / e
Permissible conductor cross-sections for auxiliary terminals
Solid
Finely stranded with end sleeve
Cable lug in accord. with DIN 46231
Push on receptacle B2.8
AWG wires, stranded and solid
Stripped length
Tightening Torque
Installation of auxiliary conductor terminal 3TX7500-0A (accessory) see Fig. IIIa.
For circuit diagram and position terminals see Fig. IV.
AC operation
Fig. IVa
2 N0 + 2 NC;
Use 75 °C copper wire only.
**Footnote: According to IEC 60947 / VDE 0660, the types of protection mean:
"Assignment type 1": Short circuits can cause damage to the contactors making replacement of the equipment necessary.
"Assignment type 2": Easily separable contact welding but no other damage.
A5E02261839A-02
Order No.: 3ZX3012-0TS48-0AY0
2
1)
6 to 35
2.5 to 35 Max. 2 x 25
)
2
1)
10 to 35
2.5 to 35 Max. 2 x 25
)
6 to 50
2.5 to 50 Max. 2 x 35
10 to 1/0
18 to 1/0 Max. 2 x 1/0
18 to 20 mm / 3/4 in
4 to 6 Nm / 36 to 52 lbf·in
3TS47 / 3TS48
2
2)
10 to 35
)
10 to 50
12 x 3
7 to 1/0
M6 x 20
4 to 6 Nm / 36 to 52 lbf·in
2 x 0.5 to 1; 2 x 1 to 2.5; 1 x 4 mm
2 x 0.5 to 1; 2 x 0.75 to 2.5 mm
2
2 x 1 to 1.5 mm
2
2 x 0.3 to 1.5 mm
2 x 18 to 12
10 mm / 0.4 in
0.8 to 1.4 Nm / 7 to 12 lbf·in
Fig. IVb
4 NO + 4 NC
DIN VDE 0660, IEC 60947-4-1, Q/320500 SMS 009, GB14048.4
Operation
Observe operating voltage (see rating plate of magnet coil).
The operating state of the contactor is shown at the position indicator; see Fig. V.
After a short circuit the main contacts and the arc chute must be checked.
Maintenance
The following components can be replaced: Main contacts, arc chute, magnet coil,
auxiliary contact blocks. - For Order Nos. see Catalog.
Cleaning
Remove dust by suction.
Auxiliary contact block
For replacement see Fig. VIa / 1, 2, 3; for extension see Fig. VIb / 4, 5, 6.
Arc chute and main contacts
Remove arc chute (Fig. VII / 1, 2, 3). Check main contacts (Fig. VII / 4). If neces-
sary, separate slightly welded contacts with a screwdriver.
Dark or rough contacts can still function. Do not refinish or grease them. If the con-
tact facings are so badly eroded that the carrier material is visible (Fig. VII / 4a), all
contacts must be replaced.
For replacement of contacts see Fig. VII / 5, 6, 7.
It is not necessary to disconnect the main conductors. Check the arc chute and
replace it if necessary.
With the arc chute removed, the contactor is mechanically interlocked. Coil excita-
tion is not permitted under these conditions.
Magnet coil
For coil replacement see Fig. VIII
Ensure that the pole faces of the magnet coil are clean. Do not use grease solvents
or sharp objects for cleaning.
Technical Data
Weight
Permissible ambient temperature
- Operation
- Storage
Main circuit
Rated insulation voltage U
Rated output AC-3
at
230 V
240 V
400 V
415 V
500 V
690 V
Rated operating current
I
/ AC-1 (55 °C)
e
I
/ AC-3
e
I
/ AC-3
e
I
/ AC-3
e
Short Circuit protection
Degree of protection to DIN VDE 06601, part 102A /
IEC 60947-4-1**
- Assigtnment type 1
- Assignment type 2
- non-welding I
<100 x I
k
2
- non-welding I
³100 x I
k
2
Auxiliary circuit
Rated operating current I
Short-circuit protection
- Fuse-links NEOZED and DIAZED
- Circuit-breaker
For further data and accessories see Catalog.
3TS47, 3TS48
approx. 1.4 kg
-25 °C to +55 °C
-50 °C to +80 °C
AC 1000 V
i
3TS47
kW
kW
kW
kW
kW
kW
3TS47
to 690 V
A
to 400 V
A
to 690 V
A
at 690 V
A
Fuse-links, gL (gG)
3TS47
A
A
A
e
A
e
/ AC-15 / AC-11
5.6 A at AC 230 V
e
gL (gG)
C
B
Last update: 01 April 2011
English
3TS48
18.5
22
20
24
30
37
25
34
30
41
39
56
3TS48
90
95
65
75
45
63
6
6
3TS48
160
160
100
100
50
63
63
80
16 A
10 A
16 A

Publicidad

loading

Resumen de contenidos para Siemens 3TS47

  • Página 1 Rated operating current 3TS47 3TS48 Without box termina / AC-1 (55 °C) to 690 V -see Fig. IIIc 3TS47 / 3TS48 / AC-3 1 or 2 conductors can be connected to 400 V / AC-3 10 to 35 to 690 V...
  • Página 2 Sin borne tipo marco 690 V Ver Fig. IIIc Intensidad de servicio asignada 3TS47 3TS48 3TS47 / 3TS48 Pueden conectarse 1 ó 2 conductores / AC-1 (55 °C) hasta 690 V 10 a 35 Flexible con terminal macho (mm / AC-3...
  • Página 3 690 V sem terminal de caixa Corrente nominal de funcionamento 3TS47 3TS48 -ver fig. IIIc 3TS47 / 3TS48 / AC-1 (55 °C) até 690 V podem ser ligados 1 ou 2 condutores / AC-3 até 400 V 10 até 35...
  • Página 4: Руководство По Эксплуатации

    Номинальный рабочий ток 3TS47 3TS48 Без рамочного зажима / AC-1 (55 °C) -смотри рис. IIIc до 690 B 3TS47 / 3TS48 1 или 2 провода могут соединяться / AC-3 до 400 B 10 ~ 35 Скрученный провод с наконечником (мм / AC-3 до...
  • Página 5 240 V DIN 46228 中的第一部分。 400 V 在安装接线盒前 ( 见图 IIIb),必须移开灭弧室 (见图 VII / 1, 2, 3) 415 V 不带接线盒的 500 V 见图 IIIc 690 V 3TS47 / 3TS48 一或二根导线能被连接 3TS47 3TS48 额定工作电流 2) 10~35 mm 具有柱状接线片的细绞合线 / AC-1 (55 °C) 至...
  • Página 6 II a 22,5° 22,5° 26,5 90° 90° 10,5  ?4,8 mininum clearance from earthed parts: 10 mm distancia de aislamiento mínima de componentes conectados a tierra: 10 mm distância mínima de isolamento dos componentes ligados à terra: 10 mm Минимальное расстояние до заземленных частей - 10 мм 对接地部件的最小距离...
  • Página 7  90•  90•  90• 3TS47: 1.3 Nm / 11 lb·in 3TS48: 1.9 Nm / 17 lb·in 3TF46: 1,3 Nm/11 lb.in VIII a 3TF47 1 9 N /17 lb i VIII a Technical Assistance: Telephone: +49 (0) 911-895-5900 (8°° - 17°° CET)

Este manual también es adecuado para:

3ts48