Recommended Suppression Techniques and Values
DC Inductive Load Suppression
Required items
1
One (1) general-purpose diode with at least a 1 A 100 V- rating (e.g., 1N4002 or equivalent)
Two (2) wire nuts or connectors
DC Load Suppression
Schematic
CCO
NO
COM
NC
1N4002
Diode
Low-Voltage Power Supply
+
AC Inductive Load Suppression
Required items
1
One (1) 0.1 µF non-polarized capacitor with at least a 50 V~ rating (NOTE: DO NOT use an electrolytic or other polarized
capacitor with this AC circuit; DO use an AC-rated film or ceramic capacitor)
One (1) 1 kΩ resistor with at least a 0.5 W power rating
Two (2) wire nuts or connectors
AC Load Suppression
Schematic
CCO
NO
COM
NC
Resistor
Capacitor
Low-Voltage Power Supply
~
These suppression components are suggested as general guidelines. Contacting the load manufacturer is STRONGLY recommended as
1
they are best-suited to provide specific details on proper component selection for the load in use.
Orientation of diode is important. Make sure cathode (side with ring) is connected to the positive side of the DC power supply.
2
Actual wiring depends on specific product. Refer to the product rating for current and voltages.
3
Application Note #434
PowPak
Module
3
®
Inductive
Load
PowPak
Module
3
®
Inductive
Load
CCO
V
R
0–24 V-
1 A
0–24 V~
1/2 A
+
Low-Voltage Power Supply
CCO
V
R
0–24 V-
1 A
0–24 V~
1/2 A
Capacitor
~
Low-Voltage Power Supply
2
2
DC Load Suppression
Wiring Diagram
1N4002
Inductive
Diode
Load
AC Load Suppression
Wiring Diagram
Resistor
Inductive