WARNING! This adjustment affects the safety of the automatic system.
Check that the thrust applied onto the wing complies with regulations in force.
The motor torque can be adjusted only when the gate is still. The power levels are 6.
- Press the POT push-button for 1s and release it.
- At each pressing of the POT push-button , power is increased. This increase is shown by the indicator bar
LED "POWER".
- Once the maximum power is reached, if the push-button is pressed again, the sequence restarts from the
minimum power value.
- Store the desired value in memory by keeping the POT button pressed for 5s, the D1 green LED stays on
during the 5s. At end of storage, this LED switches off.
TCA
It allows the adjustment of the automatic closure time. Check Dip-Switch N°2= ON.
This function can be adjusted between 1 s minimum and 250 s maximum.
TL
It allows the maximum time of the opening and closing phases.
This function can be adjusted between 5 s minimum and 70 s maximum.
Braking :
During the last 14 seconds of the preset operating time, the control unit carries out a braking
operation by reducing the motor speed.
It is recommended to preset the TL operating time 7 seconds longer than the stroke time in order
to allow a 7-second braking.
If the braking function is not required, increase the TL for a time longer that 14 seconds with
respect to the stroke time.
DIP 1
The operating mode of "Pulsante P.P." (Step-by-step push button) and of the transmitter is
selected.
Off: operation: Open > Stop > Close > Stop
On: operation : Open > Stop > Close > Stop
DIP 2
The automatic closure is enabled or disabled.
Off: disabled automatic closure
On: enabled automatic closure
DIP 3
The multi-flat function is enabled or disabled.
Off: disabled multi-flat function.
On: enabled multi-flat function. The P.P. (Step-by-step) impulse or the impulse of the transmitter
have no effect in the opening phase.
DIP 4
Forewarning flashing light enabled or disabled
Off: disabled forewarning flashing light.
On: enabled forewarning flashing light. The flashing light is activated 3 s before the starting of the
motor.
DIP 5
Motor start pickup
Off: disabled pickup.
On: enabled pickup. The maximum torque of the motor is for approx. 1 sec. from start.
DIP 6
Activation of FTC input in the opening phase.
Off: No activation. In the opening phase, the FTC input (photocells) is disabled.
On: Temporary stop. In the opening phase, the FTC input (photocells) is enabled.
If an obstacle is detected, the wing movement stops, until the photocells are deactivated.
DIP 7
Function of APRE (OPEN) input
Off: This input works as "OPEN" control
On: This input works as "PEDESTRIAN" control. It provides an opening movement of 15s.
DIP 8
The electronic brake is enabled or disabled
Off: Electronic brake disabled.
On: Electronic brake enabled. For heavier gates, this function is to be enabled in order to
compensate the gate wing inertia in case the gate stops or reverses its movement.
8
Adjustment of the motor power
Functions of Trimmers
Dip-Switch functions SW2 "SELECT"