ENG
3.7
Technical data
3.7.1
Refrigeration circuit
Designation
Cooling capacity at A35 / A35 */*
Cooling capacity at A50 / A35 */*
Refrigerant type *
Refrigerant quantity *
Temperature setpoint (factory setting)
Fault indication: Switch cabinet interior
temperature
(factory setting)
Ambient air temperature
Switch cabinet interior temperature
Air volume flow, exterior circuit
Air volume flow, interior circuit
Condensate separation
Sound pressure level (1 m)
Tab. 6: Refrigeration data
*
Data on the type plate.
NOTE
The use of optional filter mats reduces the cooling capacity
Operating Manual | Roof-mounted Cooling Unit | Multi Controller (MC) – 115 V | 086100029c
Q
0
Q
0
SC-Controller: > +50 °C (+122 °F)
MC-Controller: > +52 °C (+125.6 °F)
+15 °C (+59 °F) to +55 °C (+131 °F)
+25 °C (+77 °F) to +45 °C (+113 °F)
Condensate evaporator
Model DTT 6401
2100 W
1600 W
R134A
750 g
+35 °C (+95 °F)
1970 m³/h
990 m³/h
≤ 62 dB(A)
27/28