3. Configure the Valve
NOTE: Valve setup requires an installed controller, a computer or
tablet, and a router with active internet service.
NOTE: Valves which have been recently installed, or have not been
used for some time should be exercised before running tests or
setting the maximum temperature.
NOTE: The maximum water temperature to the outlets is limited to
120°F (49°C). The valve will automatically shut down if the
temperature exceeds 120°F (49°C).
To configure valve setup, refer to the guide on the K-99695
controller product page at www.us.kohler.com.
Before Operating the System For the First Time:
Download and install the latest software for connected components.
This may take an hour or more to complete based on system
configuration and internet connection speed. Do not disconnect the
power from any components during software download and
installation.
Troubleshooting
WARNING: Risk of electric shock. Disconnect power before
servicing.
NOTICE: Valve maintenance should be performed by a KOHLER
Authorized Service Representative.
NOTE: For additional valve troubleshooting, refer to the valve
installation guide.
This troubleshooting guide is for general aid only. For service and
installation issues or concerns, call 1-800-4KOHLER.
Troubleshooting Table
Symptoms
Probable Cause
1.
Valve will not
A. Valve is not
turn on.
B. Power supply
Kohler Co.
Recommended Action
A. Plug the valve into
plugged into the
an outlet.
outlet.
B. Check power supply
connection to the
connections to the
valve may be loose
valve and reconnect
or disconnected.
if needed.