TYPE OF DIAGNOSTIC AND LED STATUS CHART
GN SMART - LOAD AND CURRENT DETECTION
- 84139150N /84139120N / 84139130N
LED CONTROL
STATUS
No power
Open Mains
Normal operation (without control)
Normal operation
Open load (without control)
Open load
Short Circuit SSR (without control)
Short Circuit SSR
GNR SMART MODULE - 84050040N
STATUS
ALARM
No Power
Normal Operation
Open Mains/Load
Blown fuses
Short Circuit SSR
Partial Load Break
Test/ Teach Mode
Teach Value Storing
IMPORTANT CONSIDERATIONS
Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by Crouzet for any consequences arising out
of use of this manual. Be sure to use input and output voltage within operating ranges.
!
WARNING:
The product's side panels may be hot, allow the product to cool before touching. Please follow mounting instructions. Failure to follow these instructions can result
in serious injury or equipment damage.
WARNING
RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE
•
Confirm that the product power supply voltage and its tolerances are compatible
with those of the electrical network.
•
The product's side panels may be hot, allow the product to cool before touching.
•
Follow proper mounting instructions including torque values.
•
Do not allow liquids or foreign objects to enter this product.
For more information please go to www.couzet.com
MAINS
CHARGE
THYRISTOR
STATUS
No
-
No
-
Yes
OK
OK
Yes
OK
OK
Yes
Open
OK
Open
OK
Yes
Yes
OK
Short circuit
Yes
OK
Short circuit
LOAD
DIAGNOSTIC
ON
INPUT
CURRENT
OUTPUT
0A
Open (0V)
= Iteach
Open (0V)
0A
Ton=100 ms
Toff=100 ms
0A
Closed (+VDD)
< Iteach*0.84
Closed (+VDD)
Ton=1 s
Toff=1 s"
Iteach = Value of current stored by «Teach-in» button
SSR - SMART
LED ALARM
DIAGNOSTIC
STATUS
OUTPUT
-
Open
-
Open
Closed
Closed
Open
Open
Open
Open
GNR SMART MODULE - 84050043N
STATUS
No Power
Normal Operation
Open Mains/Load
Blown fuses
Short Circuit SSR
Over Load
Partial Load Break
Test/ Teach Mode
Teach Value Storing
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Turn off power supply before working on this equipment.
Failure to follow these instructions can result in death, serious
INSTALLATION SHEET
GN SMART - CURRENT DETECTION
- 84136120N
LED ALARM
INPUT
Load Current > 4 A
ON
0.8A < Load Current < 4 A
ON
Load Current < 0.8 A
ON
Load Current > 0.8 A
OFF
(Short circuit SSR)
Load Current < 0.8 A
OFF
LOAD
ALARM
ON
INPUT
CURRENT
0A
= Iteach
0A
0A
> Iteach*1.16
< Iteach*0.84
DANGER
!
injury or equipment damage.
DIAGNOSTIC
STATUS
OUTPUT
Closed
Closed
Open
Open
Open
DIAGNOSTIC
OUTPUT
Closed (+VDD)
Closed (+VDD)
Ton=2 s
Toff=1 s
Ton=1 s
Toff=1 s
Ton=200 ms
Toff=200 ms
Ton=200 ms
Toff=2 s