aermotor VNA2 Serie Manual De Instalación Y De Operación página 6

Bombas de chorro verticales
Ocultar thumbs Ver también para VNA2 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation
Pump
mounted
on Casing
Adapter
Casing Adapter
(Use gasket
between adapter
and pump flange)
Well Casing
serves as
Drive Pipe
Suction
Pipe
Venturi
Nozzle
Ejector
Cup
Leathers
2357b 0697
Figure 8
SINGLE PIPE EJECTOR INSTALLATION
Single pipe installations require (see Figure 8):
a. Galvanized steel pipe
b. Leather packer-type ejector with built-in foot valve
c. Turned couplings (supplied with packer-type ejector)
d. Well casing adapter.
Step 1. Connect ejector to first length of pipe. Use pipe joint compound
Step 2. Lower pipe into casing. Use special turned couplings (included
NOTE: Fill pipe with water as each length is added to be sure foot valve
Water level
with pump
and connections do not leak.
running
Step 3. Add lengths of pipe until the ejector reaches the proper depth.
IMPORTANT: as a guide, the ejector should be set at least 10 to 20 feet
below the lowest water level with pump running, if possible, but always at
least 5 feet above the bottom of the well (see Figure 8).
Step 4. To properly seat the cup seals, after the ejector is correctly posi-
10 to 20 Feet
Step 5. With ejector set, install well casing adapter. Remove pipe holder.
5 Feet
DISCHARGE PIPE SIZES
or more
Step 1. If increasing discharge pipe size, install reducer in pump discharge
Step 2. When the pump is set away from the points of water use, the dis-
sparingly on male threads.
with 2" single pipe ejector package) to increase water flow. Use
pipe joint compound sparingly on male couplings threads.
(Your well driller should supply this information.)
tioned move the assembly up and down slightly. Water pressure in
the casing will then soak the cup seals (see Figure 8). They should
seal within 2-3 hours after installation.
Align locating lugs and tighten adapter to form seal with well
casing.
port. Do not increase pipe size by stages.
charge pipe size should be increased to reduce pressure losses
caused by friction.
• Up to 100 ft run: Same size as pump discharge port.
• 100 ft. to 300 ft run: Increase one pipe size.
• 300 ft. to 600 ft run: Increase two pipe sizes.
6