Multifunction instrument with 1 input
"Easy Connect" for 3 Rogowski probes

9. COMMUNICATION

RS485 Modbus wiring diagram:
ETHERNET
RJ45
(3)
RS485 Modbus wiring diagram with Mini Web Server:
RS485: Required use of Belden 9842 or Belden 3106A wire (or equivalent) for a maximum bus length of 1000 m, or Category 6 wire (FTP or
(1)
UTP) for a maximum length of 50 m
120Ω terminating resistor inside the instrument (it can be set in the SETUP menu)
(2)
Ethernet: Cat. 6 (FTP/UTP)
(3)
The "SG" terminal must never be connected to the earth
(4)
Mbus wiring diagram:
MASTER
MBUS
Communication tables
- The MODBUS and MBUS communication protocols are available on the
Technical data sheet: IDP000264EN_05
SXIIP
RS-485
+ – SG
2
(4)
SXWS10/SXWS32
RS-485
+
– SG
(4)
3
MBUS
A B
(5)
Non-polarized connections
A two-wire standard telephone cable (JYStY N*2*0.8 mm)
(5)
Updated: 17/03/2021
Code: MK96R63DT – MK96R63MT
MK96R125DT – MK96R125MT
Model: NEMO 96 EC
MK96R....
N°1
+ – SG
(4)
MK96R....
N°1
+
– SG
(4)
MBUS
A B
http://www.imeitaly.com
MK96R....
N°2
+ – SG
(4)
MK96R....
N°2
+
– SG
(4)
MBUS
A B
site.
Created: 21/11/2019
MK96R.....
N°n
+ – SG
(4)
MK96R....
N°n
+
– SG
(4)
6 / 6