INSTALLATION INSTRUCTIONS
E-FFC14, E-FFC19, E-FFC24, and
E-FFC36 Series
2"
ADJUSTABLE FITTER MOUNTING
(Requires use of E-ACS-FFC Accessory)
1.
Remove splice compartment cover from fitter by removing (2) #8
cover screws. See Figure 2.
2.
Route fixture ground wire (green), common wire (white) and
voltage wire (black) through open end of upper fitter and into
splice compartment.
3.
Fasten upper fitter to the fixture using (4) Allen head fasteners and
Allen wrench included in accessory kit. Tighten bolts to
132 in-lbs (14.9 N•m).
4.
Feed supply leads up through the tenon that the fitter will be
mounted on.
5.
Route supply leads through open end of lower fitter and into splice
compartment.
NOTE: It may be necessary to disassemble the upper and lower
portions of the adjustable fitter in order to run the leads into the
splice compartment. If disassembly is necessary, remove the ³⁄
(10 mm) bolt and lock washer inside the splice compartment and
route leads into splice compartment. Reassemble upper and lower
halves and replace ³⁄
" bolt and lock washer. Do not fully tighten
8
bolt at this time.
6.
Strain relief is required for electrical connections on slip fitter
mounts at height of 25' (7.6 mm) and above. If strain relief is
necessary, tie a knot in the supply leads above the hole where
the leads enter the splice compartment to reduce the strain on the
connections. Make sure the knot will not slip through opening in
splice compartment.
7.
Slip the lower fitter over a 2 ³⁄
tenon and securely tighten the (2) Allen head set screws with a
³⁄
" Allen wrench to 140 in-lbs (16 N•m).
16
8.
If ³⁄
" bolt holding the two halves of the adjustable fitter together
8
was not loosened in Step 5, loosen the bolt (do NOT remove the
bolt) at this time.
9.
Tilt the fixture to the desired angle and tighten the ³⁄
to 19 ft-lbs (25 N•m) to lock the fitter in place.
10. Make the wiring connections in the splice compartment per the
Electrical Connections section.
11. Replace the splice compartment cover and gasket that were
removed in Step 1. Tighten cover screws to 30 in-lbs (3.5 N•m)..
ELECTRICAL CONNECTIONS
Fixture is equipped with universal volt driver 120-277V
(ie. 120V, 208V, 240V or 277V)
PHASE TO NEUTRAL WIRING 120/277V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply common to fixture neutral (white) lead.
3. Connect supply Vin to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no
wires are pinched.
PHASE TO PHASE WIRING 208/240V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply L1 (Hot) to fixture neutral (white) lead.
3. Connect supply L2 (Hot) to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no
wires are pinched.
" (60 mm) O.D. heavy wall pipe or
8
" (10 mm) bolt
8
www.e-conolight.com
Document:
LPN00670X0003A0_A
Created By:
TMT
FIGURE 2
"
8
(2) #8
Screws
CAUTION: Changes or modifications not expressly approved could
void your authority to use this equipment.
This device complies with part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Changes or modifications not expressly approved could void your
authority to use this equipment.
This equipment has been tested and found to comply with the limits for
a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to
radio communications. However, there is no guarantee that interference
will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following
measures:
—Reorient or relocate the receiving antenna.
—Increase the separation between the equipment and receiver.
—Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
—Consult the dealer or an experienced radio/TV technician for help.
CAN ICES-005 (B)/NMB-005 (B)
|
888.243.9445
|
FAX: 262.504.5409
Date
ECO#
Gasket
Upper Fitter
Gasket
Cover
³⁄
"
Bolt
8
(4) Allen
Bolts
Splice Compartment
FCC NOTICE Class B
10-30-2019
011204
Lower
Fitter
Open End of
Lower Fitter
O-Ring

Publicidad

loading

Este manual también es adecuado para:

E-ffc19 serieE-ffc24 serieE-ffc36 serie