Multifunction instrument with 1 input
"Easy Connect" for 3 Rogowski probes
6. OPERATING DATA
6.1 ELECTRIC
MK96R63DT
Currents:
MK96R63MT
Ref. Current
Min. Current
Max. Current
Voltages:
- Three-phase voltage: 3x230V / 3x400V ±15%
Rated frequency:
- F
: 50...60Hz
n
- Permitted variation: 47...63Hz
Connectable section:
Terminals
Rigid wire
0,05 ÷ 4,5 mm²
Flexible wire
0,05 ÷ 2,5mm²
Necessary tools:
- Terminals: 2,5 mm flat or Phillips PH0 screwdriver
MECHANICAL
6.2
Depht of the terminals:
- Terminal depth: 8mm
- Lengths of the wire stripping: 8mm
Screw head:
- Phillips screw
Recommended torque:
- Voltage connection terminals (V1, V2, V3, N), auxiliary supply: 0,6 Nm
Technical data sheet: IDP000264EN_04
MK96R125DT
MK96R125MT
10A
20A
0,5A
1A
63A
125A
Without bush
Updated: 23/09/2020
Code: MK96R63DT – MK96R63MT
MK96R125DT – MK96R125MT
Model: NEMO 96 EC
7. GENERAL FATURES
(continued)
Front marking:
- In indelible digital printing.
Connection terminal board marking:
- In indelible pad printing
CURRENT
A
B
1
C
INPUT
V
V
V
N
1
2
3
Display:
- Type: backlit LCD
- Reading points: 10.000 4 digits (12mm digit height)
- Energy count: 8 digit numerator (8mm digit height)
- Resolution: automatic
- Decimal point: automatic
- Update time: 1 sec.
Display of the value and programming:
- By means of the front keypad, 4 pushbuttons
).
manual
- Access protected by identification code (
Measurements and precision in conformity with
- Current: cl.1
- Voltage: cl.0,5
- Frequency: ± 0,1 Hz
- Instantaneous total active power, phase, average value and max.
average value : cl.1
- Instantaneous total reactive power, phase, average value and max.
average value : cl.2
- Instantaneous total apparent power, phase, average value and
max. average value : cl.1
- Power Factor : cl.1
- Total active energy, positive and negative: cl. 1
- Total reactive energy, positive and negative: cl.2
Average power:
- Measurement: current-apparent, reactive, active power
- Calculation: moving average, on the selected period
- Average time: 5/8/10/15/20/30/60min.
Created: 21/11/2019
+
CURRENT
SG
1
C
INPUT
V
V
V
N
1
2
3
(please refer to the user
)
predefined code 1000
EN/IEC 61557-12
3 / 6