HUBBELL STAINLESS STEEL SLOPED BLANK ENCLOSURE
This enclosure is listed to the requirements of Outdoor/Indoor Type 3 (Weather
Type 3RX (Rain Tight and Corrosion Resistant), Type 4
installations and Outdoor/Indoor IP69K (High Pressure, High Temperature and Dust)
GENERAL INFORMATION
1. NOTICE: For installation by a qualified electrician in accordance with National Electrical Code
the Canadian Electric Code, local codes and the instructions on the following pages.
2. CAUTION: RISK OF ELECTRIC SHOCK. More than one supply disconnect switch may be
required to de‑energize this equipment before servicing. Disconnect ALL power supplies to
enclosure before exposing interior.
3. NOTICE: Separate overcurrent protection must be provided in accordance with National Electrical
Code
®
Article 240 or Canadian Electrical Code, Section 8 and 14, as appropriate.
CLEANING PROCEDURES
4. Follow the general cleaning procedures established by your facility for your specific application.
5. This product is certified by NSF
the following cleaning practice is recommended for this product:
CAUTION: Use only chemicals and cleaning solutions that are safe for use with silicone and
neoprene gaskets.
CAUTION: Risk of electric shock. Do not clean this product while undergoing electrical maintenance or service.
a. Use hose‑directed water or cleaning solution to remove any collected soil or contaminants from behind this enclosure. Care must be
exercised to apply the water spray in such a manner to completely wash the area between the enclosure and the wall onto which it is
mounted.
b. Use hose‑directed water or cleaning solution to wash away soil or contaminants from the exterior surfaces of the enclosure.
c. CAUTION: Do not direct or concentrate high pressure water or cleaning solution on the lid and box gasket seams or on any applied
labels.
d. After using hose‑directed water or cleaning solutions, use a clean damp cloth to manually remove any soil or other contaminants from
the gasket seam area or other necessary areas.
e. Use a dry clean cloth to wipe away any excess water.
INSTALLATION INSTRUCTIONS
This enclosure may be mounted for single or dual bottom conduit entrances.
A. MOUNTING INSTRUCTIONS
1. For Type 3, Type 3R, Type 3X, Type 3RX, Type 4, Type 4X, Type 12 and IP69K applications, enclosure must be mounted by means of
mounting feet. DO NOT drill, punch or nail mounting holes through the enclosure.
2. Mounting feet will accept up to ¼" or 6 mm screws (not provided). Mounting pattern for HBLDSSRNK3 and HBLDSSRNK6 are shown in
Fig M‑5 and M‑6 respectively.
3. Remove the enclosure cover.
4. Prior to drilling holes for conduit(s) remove GROUNDING buss by sufficiently loosening the center mounting screw. (see Fig. M‑2 and
M‑3)
5. Bottom feed is shown in Fig. (M‑2 and M‑3).
6. Use appropriately rated conduit hub for required environmental rating of the application.
7. Install a conduit fitting rated Type 3, Type 3R, Type 3X Type 3RX, Type 4, Type 4X, Type 12 and/or IP69K depending on required
environmental application. Be sure that the "O" ring is properly seated in its groove. Tighten the conduit fitting.
8. Any unused conduit entrance holes must be sealed with Listed/Certified closure plugs rated Type 3, Type 3R, Type 3X, Type 3RX, Type
4, Type 4X, Type 12, and/or IP69K depending on required environmental application.
B. DUAL CONDUIT ENTRY: See Fig M‑2. SINGLE CONDUIT ENTRY: See Fig M‑3
1. Drill or punch a 1.109" dia. (¾" trade size) at the desired conduit entrance location. Use drill spots to accurately locate hole.
2. If required use ONLY a Listed / Certified Breather Drain rated for Type 3, Type 3R, Type 3X, Type 3RX, Type 4, Type 4X, Type 12 and/or
IP69K depending on required environmental application. Punch or drill a hole sized in accordance to Breather Drain installation instruction
through the bottom wall of the enclosure (see Fig M‑4).
WIRING INSTRUCTIONS
1. Use conductors having 90°C or higher rated insulation and sufficient ampacity in accordance with the 60°C column of National Electrical
Code® Table 310.15(B)(16) or Canadian Electrical Code Table 2.
2. CAUTION: USE COPPER CONDUCTORS ONLY.
3. DO NOT TIN CONDUCTORS.
4. Make sure the connected equipment rating does not exceed the rating of this device. See GENERAL INFORMATION (#3) regarding
overcurrent protection.
5. GROUNDING terminals will accept wire size range from # 6‑16 AWG (HBLDSSRNK3), #10‑4 AWG (HBLDSSRNK6), See GENERAL
INFORMATION (#1) regarding GROUNDING conductor sizing.
6. Strip length of all GROUNDING conductors is ½ inch (13 mm).
7. For respective catalog number, tighten GROUNDING buss screws as follows in Table 1:
Catalog Number:
Terminal Screws:
HBLDSSRNK3
14.2 lb•in (1.6 N•m)
HBLDSSRNK6
35.4 lb•in (3.9 N•m)
8. Assure that there are no loose wire strands.
9. Reinstall cover. Tighten the four cover screws to 24 lb•in (2.7 N•m). Make sure the sealing O‑rings are in place under the screw heads.
10. An additional DANGER label (D64558) has been supplied loose with this product as a convenience. Apply label to the outside of the front cover
if the product application does not pose the risk of the label being removed through cleaning, hose down or any other means.
11. Consult factory for auxiliary contact availability.
Wiring Device-Kellems
Hubbell Incorporated (Delaware)
1-800-288-6000
Shelton, Ct 06484
www.hubbell-wiring.com
PD2737
2/16
(PAGE 1)
(Watertight),
®
International for use in food processing Splash Zone Areas,
Table 1
Mounting Screw:
4.4‑8.9 lb•in (0.5‑1.0 N•m)
21.2 lb•in (2.4 N•m)
Resistant),
Type 3R (Rain Tight), Type 3X (Corrosion resistant)
Type 4X (Watertight, Corrosion Resistant), Indoor Type 12 (Dust Tight)
®
or