Dead Band (Dual Set Points); Change Temperature Setting(Single Set Point) - LG PREMTC00U Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

OPERATION INSTRUCTIONS - Sub Function
14
Press the
button for 3 seconds. You can
enter to sub function setting mode and press
the
button repeatedly to change the sub
function mode in the following order.
Setback temperature
Override time
setting
setting
Dead band setting or
Change temperature
setting
Vane angle control
WLAN module
Heater
access
point mode
h Some functions may not operate depending
on the product.
h Dead band setting – When it connects with
an dual set points control product.
Change temperature – When it connect
with single set point control product.
Setting the setback temperature
1 Press
button for 3 seconds.
2 Press
button to move the setback
mode.
3 Press
button to select cool/heat
temperature.
4 Press
button to change the
temperature.
5 Press
button to set temperature.
6 Press
button for 3 seconds.
Setting the override time
1 Press
button for 3 seconds.
2 Press
button to move the override
mode.
3 Press
button to select override time.
4 Press
button to set override time.
5 Press
button for 3 seconds.
h You can set in units of 30 minutes.
OPERATION INSTRUCTIONS - Sub Function

Dead band (Dual set points)

This function sets the minimum difference
between heating and cooling set points.
h This function is used in connection with the
dual set points control product.
1
Press
button for 3 seconds.
2
Press
button to move the dead band
mode.
3
Press
button to change the dead band
temperature. (0 ~ 10°F/0 ~ 5°C)
4
Press
button to set temperature.
5
Press
button for 3 seconds.
Change temperature setting
(Single set point)
Change temperature is the function to setup
air-cooling and heating drive automatically
changeable according to the temperature at
single set point auto operation mode.
h This function is used in connection with the
single set point control product.
15
1
Press
button for 3 seconds.
2
Press
button to move the change
temperature setting mode.
3
Press
button to change the
temperature. (2 ~ 14°F/1 ~ 7°C)
4
Press
button to set temperature.
5
Press
button for 3 seconds.
Example of using change temperature
Condition
1) Mode: Auto mode
2) Temperature: 72°F(22°C)
3) Change Temperature: 6°F(3°C)
h In case of the above conditions, it operates
as in the graph.
① : Cooling operation start
② : Heating operation start
Temp(°F/°C)
78°F(25°C)
72°F(22°C)
66°F(19°C)
h This function may not work in some
products.