SWITCH OFF THE CIRCUIT BREAKER (Step: 1)
MOUNT THE SMART METER (Step: 2)
6
7
SET UP THE TERMINATING RESISTOR (Steps: 6-7)
CU Wire
0,05 mm²
Manufacturer manual
0,4 Nm
e. g. Ohmpilot, Battery
Bypass (cable)
T
M-
3
5
11
12
ENTER THE SETTINGS (Step: 11)
SETUP THE PASSWORD (Step: 12)
kWh
000
000
kW
3a
1 PHASE, 2 WIRES (Step: 3a)
L
N
Manufacturer manual
Inverter
max. 300 m
13
SETUP THE ADDRESS (Step: 13)
Factory default: 2633
Factory default: Modbus Address 001
PASS
2633
2
P10
P1
PrG
3b
1 PHASE, 2 WIRES (Step: 3b)
8
MOUNT THE CONNECTOR COVERS (Step: 8)
D+
D-
-
T
M+
M-
GND
T
6
Smart Meter
0 0 1
7
14
EXIT THE SETTINGS (Step: 14)
AddrESS
6
001
4
PrG
P14
4
MOUNT THE PROTECTIVE COVER (Step: 4)
9
SWITCH ON THE CIRCUIT BREAKER (Step: 9)
15
START UP THE SMART METER (Step: 15)
End