3. Important Safety Warnings

CAUTION!
Save these instructions. To safely operate this unit, read and follow all instructions carefully. Read
this manual thoroughly before attempting to unpack, install or operate. Retain this manual for further
reference.
• The unit is for indoor use only.
• Do not place the unit near liquid or in an excessively damp environment.
• Do not place the unit directly in the sun or near a source of heat.
• Do not let liquid or foreign objects enter the unit.
• Ground the unit using a 2P+ ground socket.
• This equipment is not suitable for use in locations where children are likely to be present.
• The appliance is intended to be installed and operated by a skilled person (qualified electrical technician).
• CAUTION: Electrical shock risk due to the multiple supply connections.
• Use tools with insulated handles.
• Do not touch the AC mains terminals or plug. Before working on the appliance, check for hazardous voltage
between all AC mains terminals, both input plug and appliance inlet.
• When installing the unit, ensure the sum of the leakage currents of the unit and the devices it supplies does not
exceed 3.5mA.
UPS Location Warnings
Operating
Temperature
Storage
Elevation
Operating
Humidity
IP Rating
4. Installation
Inspection
Remove the unit from the shipping package and inspect it for damage that may have occurred during transport. Notify the
carrier and your dealer if any damage is found.
Connect to the Wall Outlet
Plug the Bypass PDU main input cord to an unprotected AC outlet. This connection is labeled MAIN INPUT on the PDU. The
MAIN POWER LED will illuminate when mains input is available.
Note: For models PDUBHV101U and PDUBHV201U, you may need to use your UPS system's power cable to connect the Bypass PDU to
the AC power source.
0°C to 40°C (32°F to 104°F)
-20°C to 50°C (-4°F to 122°F)
0 m to 3000 m (0 ft. to 9843 ft.): Normal Operation
0% to 95% Relative Humidity, Non-Condensing
IP20