Setup (Low alarm/no delays: default setting)
WARNING: It is essential to check settings during the process itself, and confirm
that they are correct, before regular operation commences.
Initial setup can be carried out prior to mounting into the process, but it is extremely important
to calibrate the unit and adjust the sensitivity on the product itself.
Setpoint Adjustment
Note: For more detailed instructions, please see the full manual.
Select the application type most similar to your operation, and adjust the setup conditions
accordingly.
Application
• dry solids
General
• low viscosity liquids
• hygroscopic / wet solids
• high viscosity and high
Demanding
conductivity liquids
Interface
• liquid A / liquid B
• foam / liquid
detection
Set trip point
1.
Ensure the green power LED L3 is on.
2.
Set dip switch S5 ON (set-up mode).
3.
Ensure the probe is setup conditions match the table above.
4.
If the yellow sensor status LED L1 is not on, turn the trip-point potentiometer P2
counter-clockwise until it just turns on.
5.
Turn the trip-point potentiometer P2 clockwise until LED L1 just turns off.
6.
Set dip switch S5 OFF (run mode).
Set delay interval
1.
Turn P1 clockwise to set the delay interval.
2.
Set S1 and/or S2 to OFF, to enable the delay for alarm activation/alarm de-activation.
Check the delay, using S4 to invert the signal.
If an immediate alarm output is critical, set the appropriate switch to ON, to disable the
delay.
Page EN-10
Pointek CLS200/300 (Standard) – QUICK START MANUAL
Material
sensor uncovered;
min. 100 mm (4") free space all around
sensor immersed then uncovered; but
retaining max. possible material buildup
immerse sensor in whichever material has lowest
dielectric constant
Setup conditions
7ML19985QY84