Offset Número
Nombre
de regis-
tros
50007 2
Secondary Voltage
50011 2
Primary current
50013 2
Secondary current
50019 2
Current direction L1,L2,L3
50025 2
Energy counter function
50035 2
Digital output 0.0 action
50037 2
Output 0.0 pulse type
index
50039 2
Output 0.0 pulse ratio
(Pulses per kWh/kvarh)
50041 2
Output 0.0 pulse length
50043 2
Digital Output 0.0 Timeout unsigned long
50045 2
Output 0.0 Pulse Divider
PAC1020
Manual de producto, 05/2020, L1V30610008C-01
Formato
Unidad
unsigned long
unsigned long
unsigned long
unsigned long
unsigned long
unsigned long
unsigned long
unsigned long
unsigned long
unsigned long
Rango admitido
1 ... 480V
1 ... 99999A
1, 5
0 ... 7 Bitcoded
Bit = 0 means normal,
Bit = 1 is inverse
.0 L1
.1 L2
.2 L3
0 ... 2 WORDCODED
•
0 = import
•
1 = export
•
2 = net
HIWORD kVARh Setting
LOWORD kWh Setting
0 ... 2
•
0 = no action
•
1 = switching output
•
2 = pulse output
0 ... 3
•
0 = import kWh
•
1 = export kWh
•
2 = import kvarh
•
3 = export kvarh
1-4000
30-500
0,1 ... 18000
Digital output remote
timeout = 1 ... 18000
seconds
0 = disables timeout
(default)
0 ... 3
•
0 = 1kWh
•
1 = 10kWh
•
2 = 100kWh
•
3 = 1000kWh
Anexo
A.1 Modbus
Acceso
a valor (software)
read only/read write
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
83