7. SPECIFICATIONS 
Model 
Power Supply 
Rated output current "In" 
Consumption 
Ambient temperature 
Safety class: 
Mains power fuse 
End‐of‐charge voltage 
Temperature controlled end‐of‐charge 
voltage 
End of discharge voltage 
Switch‐off threshold of the low voltage 
disconnect protection 
Maximum continuous output load 
current Imax a according to EN54‐4A2 
Maximum short time output load 
current Imax b according to EN54‐4A2 
Fuse values of the 24 V outputs 
Maximum internal battery resistance 
Battery capacity 
Ripple on charging voltage at 8 A load 
current and battery disconnected 
Cooling 
Weight 
Dimensions 
Accessories (included) 
PS-630E Version 1.0
PS-630E
Main: 230 Vac, +10% / ‐15%, 50‐60 Hz (195–253 V) 
Alternative: 24 Vdc (rechargeable battery) 
250 W (mains operation) 
1 (protective earthing) 
T6.3A slow blow 
27.2 V at 25°C 
20 V with indication BATTERY LOW  
C = battery capacity in Amperes x Hours 
Mains voltage present: = In 
At battery operation: 6 x 30 A = 180 A in total  
At mains present state, the battery will be discharged with a 
current value that exceeds In. 
Blade fuses 40A are pre‐assembled. 
 Fuse values have to be adapted to the cross section of the 
connecting leads and to the load current respectively.  
Fuse value = load current x 1.3. 
0.05 – 0.1 Ohm 
32 – 150 Amperes x Hours (Ah), also dependent on the additional 
consumer load current. 
≤ 0.2Vpp, 2Hz...20 MHz 
Temperature controlled fan 
483 x 88 x 277 mm 
1 x AC mains power cable 
1 x Battery temperature sensor 
1 x Allen wrench 
Power Manager 
PS‐630E 
8A 
‐5~40ºC 
‐20 mV/ºC 
18 V 
In – C/20;  
6.3 kg 