7. SPECIFICATIONS
Model
Power Supply
Rated output current "In"
Consumption
Ambient temperature
Safety class:
Mains power fuse
End‐of‐charge voltage
Temperature controlled end‐of‐charge
voltage
End of discharge voltage
Switch‐off threshold of the low voltage
disconnect protection
Maximum continuous output load
current Imax a according to EN54‐4A2
Maximum short time output load
current Imax b according to EN54‐4A2
Fuse values of the 24 V outputs
Maximum internal battery resistance
Battery capacity
Ripple on charging voltage at 8 A load
current and battery disconnected
Cooling
Weight
Dimensions
Accessories (included)
PS-630E Version 1.0
PS-630E
Main: 230 Vac, +10% / ‐15%, 50‐60 Hz (195–253 V)
Alternative: 24 Vdc (rechargeable battery)
250 W (mains operation)
1 (protective earthing)
T6.3A slow blow
27.2 V at 25°C
20 V with indication BATTERY LOW
C = battery capacity in Amperes x Hours
Mains voltage present: = In
At battery operation: 6 x 30 A = 180 A in total
At mains present state, the battery will be discharged with a
current value that exceeds In.
Blade fuses 40A are pre‐assembled.
Fuse values have to be adapted to the cross section of the
connecting leads and to the load current respectively.
Fuse value = load current x 1.3.
0.05 – 0.1 Ohm
32 – 150 Amperes x Hours (Ah), also dependent on the additional
consumer load current.
≤ 0.2Vpp, 2Hz...20 MHz
Temperature controlled fan
483 x 88 x 277 mm
1 x AC mains power cable
1 x Battery temperature sensor
1 x Allen wrench
Power Manager
PS‐630E
8A
‐5~40ºC
‐20 mV/ºC
18 V
In – C/20;
6.3 kg
Page 9 of 10