Panel Power Wiring Detail
Relay Wiring Detail
Wiring Information:
Line In
1
5
Strip wire:
" to
"
2
8
Neutral
Wire size: 10-12AWG
Ground
Solid/stranded copper only
*Note: Bring dedicated circuit to power
iLumin Plus lighting panel. Main power circuit
should not also power lighting.
iLumin Plus is pre-wired to power all modules
once main power is connected and energized.
Line In
Load Out
Wiring Information:
1
5
Strip wire:
" to
"
2
8
Wire size: 10-14AWG
Solid/stranded copper only
Use 75C wire insulation minimum
Load:
120-277VAC 20A per relay
Mag., Res, General Purpose
120V 20A Tungsten
120V 16A LED Ballast
277V 16A LED Ballast
Do not exceed 192A per module
Relay screw torque 1.1Nm
*Note: Branch Circuit over current protection
by others. Each relay has a 5K SCCR unless
protected by another device.
Class 1 Field Relay Terminals & Loads
20A max 10AWG min wire
16A max 12AWG min wire
12A max 14AWG min wire
Panel Network Wiring Detail
Class 2
Field installed five
wire network wire.
Run five wire
network wire to
additional iLumin
Plus panels
maintain daisy
chain
Wiring Information:
1
Strip wire:
" to
2
Wire size: 18-22AWG
Solid/stranded copper only
Class 2 wiring
Wire:
Use Cooper Lighting Solutions catalog # LCCP or LCCNP
Alternate: Beldon 1502 or 1502P or equal
*Note: Lighting control network must be run as a daisy
chain, with termination jumper in place at two ends.
0-10V Wiring Detail
Two Wire Digital Bus Wiring Detail
iLumin Plus
Class 2 Prewired
five wire network
wire.
5
"
8
Purple
Gray
Wiring Information:
1
5
Strip wire:
" to
"
2
8
Wire size: 18-14AWG
Solid/stranded copper only
Dimmer screw torque 1.1Nm
Suitable for Class 1 and Class 2
wiring per NFPA 70
Load:
100mA source/sink per channel
0-10VDC isolated (40 uA max per
circuit leakage to line)
*Note: Requires a relay (SCMR1220-NA) for
load On/Off capabilities.
Purple
Purple
Wiring Information:
1
5
Strip wire:
" to
"
2
8
Wire size: 18-14AWG
Solid/stranded copper only
Suitable for Class 1 and Class 2
wiring per NFPA 70
Load:
16VDC -225mA maximum
per channel
*Note: Load no more than 64 addressable
devices per bus. See device information for
bus power consumption.