"BR"; the detector signals alarm status when the temperature within the protected environment
exceeds 72° or when it senses a rapid temperature rise.
Note
The operating modes of the "A2S" and "BR" are not certified.
ED300
Optical-heat detector with heat sensitive element and optical smoke chamber. The combination of
values provides (in accordance with the operating mode selected via the control panel) high immu-
nity to nuisance alarms and an exceptionally sensitive detector which is capable of swift response to
fires characterized by low smoke emission.
Operating mode
Mode
The operating modes, programmable via the control panel are:
"PLUS" (pre-set); the detector signals alarm status when smoke in the protected environment
exceeds the programmed threshold (programmed as described for the ED100 model) or when
the temperature within the protected environment exceeds the programmed threshold (pro-
grammed as described for the ED200 model). Furthermore, in the event of a rise in temperature
within the protected environment, the sensitivity of the smoke chamber will be increased. This
operating mode, characterized by high sensitivity, allows detection of fires which produce a large
amount of flames but low smoke emission (e.g. combustion of alcohol or similar highly-inflam-
mable products).
"OR"; the detector signals alarm status when smoke in the protected environment exceeds the
programmed threshold (programmed as described for the ED100 model) or when the tem-
perature within the protected environment exceeds the programmed threshold (programmed as
described for the ED200 model). This operating mode, characterized by medium-high sensitivity,
allows detection of fires which generate a substantial amount of smoke but low heat emission
(slow burning fires) as well as fires which generate high temperatures and low smoke emission
(chemical products).
"AND"; the detector signals alarm status when the smoke and temperature in the protected envi-
ronment exceed the programmed thresholds simultaneously (programmed as described for the
ED100 model and ED200 model respectively). This operating mode, characterized by a low sen-
sitivity, lowers the false alarm rate and is useful in applications where either the smoke or heat
values in the protected environment may increase without the risk of fire.
Note
Given the limited response, consider the conditions in the protected environment carefully
before selecting this operating mode.
"SMOKE"; the detector assumes the characteristics of the ED100 model
"HEAT"; the detector assumes the characteristics of the ED200 model
LED
The three-colour LED (360° viewing) indicates the detector status.
Green blinking at 15-second intervals; the detector is in standby status (i.e. operating properly).
Green On solid; the LED has been activated manually from the control panel. This operation
allows easy identification of the detector.
Yellow On solid; the detector is in fault status or has detected a short-circuit in the succeeding
wiring section (short-circuit isolator open). Further details regarding the fault can be obtained
through the control panel.
Red On solid; the detector is in alarm status. Further details regarding the alarm can be obtained
through the control pane
"R" terminal
The detectors have an output (terminal "R"), for the connection of an alarm repeater LED. This LED
will activate in accordance with programming carried out via control panel.
The detector is also capable of discerning whether its repeater LED has been connected. This func-
tion provides indications (on the control panel) regarding the detectors with connected LEDs, and
also fault signals in the event of disconnection.
Description of the parts
A Detector
B Detector notch
C Thermal probe
D Red/yellow/green LED
E Optical chamber
F Technical specifications/serial-number sticker
G Removable serial-number stickers
H Cover removing hooks
I Optical chambre removing hooks
Installation
Note
For information regarding device placement, coverage and method of installation, refer to
the established standard regulations and codes relating to Automatic fire-detection
systems.
Manuale d'istruzioni / Instruction manual / Manual de instrucciones / Notice d'instructions
Enea series detectors are compliant with EN54-7: Smoke detectors – Point detectors using
the scattered light principle, light transmission or ionization (ED100 and ED300 models
only) and EN54-5: Heat detectors – point detectors (forED200 and ED300 models only),
EN54-17 short-circuit isolators.
The detectors are supplied with protective covers which help to protect them against minor damage
and dust contamination which may occur during the installation phase. The covers should not be
removed until the system is ready to start up.
The detectors can be used with one of the following compatible mounting bases:
EB0010, standard base
EB0110, standard base with removable address label plate
An example of installation using standard bases is shown opposite.
EB0020, relay base
EB0120, relay base with removable address label plate
Appropriate when the detector is to be connected to an intrusion control panel or to a control panel
using 4 wires.
Note
The two removable serial-number stickers should be taken off and one should be attached
to the mounting base and the other to the installation layout.
Once the base is located properly in its placement, place the detector unit onto the base and, with
minimum force, turn it clockwise until the detector notch [B] aligns with the base notch [K] (in order to
attach the detector to the base); turn it still further until notch [B] aligns with the second base notch
[L] (in order to allow the base to engage with the detector contacts).
When installation of all the loop devices is complete, proceed with the addressing phase. Refer to
the respective section in the control panel installation and programming manual.
Using the EDRV2000 driver
The EDRV2000 driver allows you to change the operating parameters of the detectors, check the
contamination level of the smoke chambers and also obtain accurate diagnostic data. It can operate
through the USB port of a computer furnished with the relative software programme, or can function
autonomously by way of the battery housed inside.
Each detector is capable of retaining memory (smoke and/or temperature depending on the model)
of the 5 minutes prior to an alarm. Therefore, if an alarm occurs, it will be possible to obtain infor-
mation regarding the onset of the fire by simply connecting the EDRV2000 driver to the detection
line.
For further information and details regarding use of the EDRV2000 driver, refer to the respective
handbook.
Testing and maintenance
After installation and during periodic maintenance inspections, you must carry out the following ope-
rations on each detector:
Optical smoke detector test; smoke detectors should be tested immediately after installation and
periodically during maintenance inspections in accordance with the established standard regu-
lations and codes in force. To test smoke detectors, use an approved test aerosol strictly in accor-
dance with the accompanying instructions.
Ensure that the smoke inlet ports to the smoke detection chamber are not blocked. Check the con-
tamination level of the smoke detection chamber via the control panel. If the contamination level is
high (above 50%), detach the detector from its mounting base, open the device and, using a small,
soft-bristle brush or hand-held vacuum cleaner remove all dust particles from inside and around the
smoke detection chamber.
Free the protection mesh from all contaminants.
Heat detector test; using a suitable device (e.g. hairdryer), create heat in the vicinity of the detector,
then work through the steps described in the device instruction sheet. During each periodic main-
tenance inspection, ensure that the heat element is intact and that is not obstructed by dust or paint.
J Base
If it is, using a small, soft-bristle brush or hand-held vacuum cleaner remove all contaminants.
K Base notch 1
L Base notch 2
Technical specifications
M "+" terminal
N "-" terminal
Model
O "R" terminal
Power supply
P Short-circuit reed
Current draw in standby
Q Screw locations
Current draw in alarm
Current draw by the "R" output
(internally limited)
Dimensions (DxH, standard base
included)
Weight
ED100
ED200
ED300
from19 to 30 V
200µA
10mA @27,6V
Max 14mA
110 x 46 mm
110 x 54 mm
160g, standard base included
91g, without base
Inim Electronics S.r.l. © 2021
Model
ED100
Environmental conditions
Temperature
≤ 95 % without condensation
Relative humidity
CE mark
0051
INIM Electronics s.r.l.
Via Dei Lavoratori 10 - Fraz. Centobuchi
Via Dei Lavoratori 10 - Fraz. Centobuchi
63076 Monteprandone (AP) - Italy
63076 Monteprandone (AP) - Italy
10
0051-CPR-1878
EN 54-7:2000 + A1:2002 + A2:2006
EN 54-17:2005
ED100
Intelligent analogue addressable optical smoke detec-
Intelligent analogue addressable class P heat detector
tor with short circuit isolator for fire detection and fire
with short circuit isolator for fire detection and fire alarm
alarm systems installed in buildings
Essential characteristics
Performance
Essential characteristics
Nominal activation con-
Nominal activation con-
dition/sensitivity, response delay
dition/sensitivity, response delay
PASS
(response time) and performance
(response time) and performance
under fire conditions
under fire conditions
Operational reliability
PASS
Operational reliability
Tolerance to supply voltage
PASS
Tolerance to supply voltage
Temperature resi-
PASS
stance
Durability of
Vibration resistance
PASS
Durability of
operational
operational
Humidity resistance
PASS
reliability:
reliability:
Corrosion resistance
PASS
Electrical stability
PASS
Detector class (EN54-5): A1R or B
Documents for the users
Declarations of Performance, Declarations of Conformity
and Certificates concerning to Inim Electronics S.r.l. pro-
0051
ducts may be downloaded free of charge from the web
INIM Electronics s.r.l.
address www.inim.biz, getting access to Extended Access
Via Dei Lavoratori 10 - Fraz. Centobuchi
and then selecting "Certifications" or requested to the e-
63076 Monteprandone (AP) - Italy
mail address info@inim.biz or requested by ordinary mail
10
to the address shown in this manual.
0051-CPR-1876
EN 54-5:2000 + A1:2002
Manuals may be downloaded free of charge from the web
EN 54-7:2000 + A1:2002 + A2:2006
address www.inim.biz, getting access to Extended Access
EN 54-17:2005
and then selecting "Manuals".
ED300
Intelligent analogue addressable multicriteria optical
Warnings and limitations
smoke and class P heat detector with short circuit iso-
Enea series detectors must be used exclusively with
lator for fire detection and fire alarm systems installed in
fully compliant, compatible control panels. Detectors
buildings
may not provide timely warning of fire if coverage is
limited by large obstructions (pillars, large machinery,
Essential characteristics
Performance
etc.). When installing or working on a fire detection
system, always refer to and comply with the esta-
Nominal activation con-
blished standard regulations and codes. Appropriate
dition/sensitivity, response delay
PASS
fire-risk assessment should be undertaken to deter-
(response time) and performance
mine the type of detectors required and their pla-
under fire conditions
cements.
Operational reliability
PASS
Tolerance to supply voltage
PASS
Temperature resi-
PASS
stance
Durability of
Vibration resistance
PASS
operational
Humidity resistance
PASS
reliability:
Corrosion resistance
PASS
Electrical stability
PASS
Detector class (EN54-5): A1R or B
Manufacturer's details
About this manual
Manufacturer: Inim Electronics S.r.l.
Manual code: DCMIIN1PED
Production plant: Centobuchi, via Dei Lavoratori 10
Revision: 260
63076 Monteprandone (AP), Italy
Copyright: the information contained in this document is
Tel: +39 0735 705007
Fax: +39 0735 734912
the sole property of Inim Electronics S.r.l. No part may be
copied without written authorization from Inim Electronics
e-mail: info@inim.biz
S.r.l.. All rights reserved.
Web: www.inim.biz
The persons authorized by the manufacturer to repair or
replace the parts of this system, hold authorization to
work on Inim Electronics brand devices only.
DCMIIN1PED-260-20210419
ED200
ED300
from -5 to +40 °C
0051
INIM Electronics s.r.l.
10
0051-CPR-1877
EN 54-5:2000 + A1:2002
EN 54-17:2005
ED200
systems installed in buildings
Performance
PASS
PASS
PASS
Temperature resi-
PASS
stance
Vibration resistance
PASS
Humidity resistance
PASS
Corrosion resistance
PASS
Electrical stability
PASS

Publicidad

loading

Este manual también es adecuado para:

Ed200Ed300