Dell 3750W Inicio De Su Sistema página 22

Ocultar thumbs Ver también para 3750W:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 92
Installing the Input and Ground Wires
Punch a hole in the terminal block cover for the input conduit using a Greenlee
3
device. The hole accommodates 3/4" or 1" IMC conduit.
Pull the input wire through the conduit, leaving approximately 2 ft (0.5m) of exposed wire. Attach
4
a flexible metal fitting to the end of the conduit.
Insert the conduit through the wiring access entry and attach the conduit fitting to the panel.
5
Strip 0.5" (1.5 cm) of insulation from the end of each incoming wire.
Connect the input and ground wires to the terminal block according to Table 1.
6
Table 1. UPS Wiring Specifications
Wire
Terminal
Function
Position
Input
2
* Use 5.26 mm
(10 AWG) 75_C copper wire minimum.
Replace the terminal block cover.
7
|
20
Installation and Startup
UPS Wire Function
1
Input Ground
2
L2/Neutral In
3
L1 In
®
Terminal Wire
Size Rating*
2
5.26–16 mm
2.26 Nm (20 lb in)
(10–6 AWG)
punch or similar
Tightening
Torque

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

4200wK804nH952nJ730nK805nJ739n

Tabla de contenido