Operation
Resetting Your Inverter/Charger to Restore AC Power
Your Inverter/Charger may cease supplying AC power or DC charging power in order to protect itself from overload or to protect your
electrical system. To restore normal functioning:
Overload Reset: Switch operating mode switch to "DC OFF" and remove some of the connected electrical load (ie: turn off some of the
AC devices drawing power which may have caused the overload of the unit). Wait one minute, then switch operating mode switch back to
either "AUTO/REMOTE" or "CHARGE ONLY."
Output Circuit Breaker Reset: Alternatively, check output circuit breaker on the unit's front panel. If tripped, remove a portion of the
electrical load, wait one minute to allow components to cool, then reset the circuit breaker. See the Troubleshooting section for additional
possible reasons why AC output may be absent.

Configuration

Set Configuration DIP Switches
Using a small tool, set the Configuration DIP Switches (located on the front panel, see diagram) to optimize Inverter/Charger operation
depending on your application.
Group B Dip Switches
Group A DIP Switches
A1
Select Battery Type—REQUIRED
CAUTION: The Battery Type DIP Switch setting
must match the type of batteries you connect,
or your batteries may be degraded or damaged
over an extended period of time. See "Battery
Selection," for more information.
Battery Type
AGM/Gel Cell (Sealed) Battery
Wet Cell (Vented) Battery
A2 A3
Select Low AC Input Voltage Point for Switching to
Battery—OPTIONAL*
Level
120V models
230V models
A
105V**
201V**
B
95V
182V
C
85V
163V
D
75V
144V
Switch Position
Up
Down (factory setting)
Switch Position
A4 Up & A3 Up
A4 Up & A3 Down
A4 Down & A3 Up
A4 Down & A3 Down
(factory setting)
A2
Select High AC Input Voltage Point
for Switching to Battery—OPTIONAL*
Level
120V Models
A
145V
B
135V
Level A
Level C
* Most of your connected appliances and equipment will perform
adequately when your Inverter/Charger's Low AC Voltage Input Point (DIP
Switches #3 and #4 of Group A are set to 95V. However, if the unit
frequently switches to battery power due to momentary low line voltage
swings that would have little effect on equipment operation, you may wish
to adjust these settings. By decreasing the Low AC Voltage Point, you will
reduce the number of times your unit switches to battery due to voltage
swings.
** For APS3636VR and APSINT3636VR models Level A setpoints are the
same as Level B.
5
Group A Dip Switches
230V Models
Switch Position
278V
Up
259V
Down (factory setting)
Level B
Level D