MABIS Quantum 1Kva Manual De Usuario página 41

Ocultar thumbs Ver también para Quantum 1Kva:
Tabla de contenido

Publicidad

Output Overload
(Bypass Mode)
Output Overload
(Battery Mode)
Voltage Waveform
Harmonic Distortion
Transfer Time
Power Factor
Load Crest Factor
Tabla 18. Conexiones de salida eléctricos (todos los modelos)
Modelo
1K- RT
1.5K- RT
2K- RT
3K- RT
Tabla 19. Ambiental y Seguridad (Todos los modelos)
Surge
Suppression
>200%±5%: Load transfers to Fault mode after 20 ms.
100%±5%–130%±5%: Load transfers to Fault mode after 20
minutes.
130%±5%–150%±5%: Load transfers to Fault mode after 2
minutes.
150%±5%–200%±5%: Load transfers to Fault mode after 15
seconds.
>200%±5%: Load transfers to Fault mode after 140 ms.
108%±5%–150%±5%: Load transfers to Fault mode after 30
seconds.
150%±5%–200%±5%: Load transfers to Fault mode after 300
ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
<3% THD on linear load; <5% THD on non-linear load
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
Conexiones de salida
(IEC C13-10A)*6
(IEC C13-10A)*6
(IEC C13-10A)*6
(IEC C13-10A)*6
(IEC C19-16A)*1
208/230/240 Vac Models
EN 61000-4-2, Level 4
39
Sine wave
0.9
3 to 1
Cables de salida
IEC320 C14-10A
IEC320 C14-10A
IEC320 C14-10A
IEC320 C14-10A
IEC320 C20-10A
EN 61000-2-2