Output Overload
(Bypass Mode)
Output Overload
(Battery Mode)
Voltage Waveform
Harmonic Distortion
Transfer Time
Power Factor
Load Crest Factor
Tabla 18. Conexiones de salida eléctricos (todos los modelos)
Modelo
1K- RT
1.5K- RT
2K- RT
3K- RT
Tabla 19. Ambiental y Seguridad (Todos los modelos)
Surge
Suppression
>200%±5%: Load transfers to Fault mode after 20 ms.
100%±5%–130%±5%: Load transfers to Fault mode after 20
minutes.
130%±5%–150%±5%: Load transfers to Fault mode after 2
minutes.
150%±5%–200%±5%: Load transfers to Fault mode after 15
seconds.
>200%±5%: Load transfers to Fault mode after 140 ms.
108%±5%–150%±5%: Load transfers to Fault mode after 30
seconds.
150%±5%–200%±5%: Load transfers to Fault mode after 300
ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
<3% THD on linear load; <5% THD on non-linear load
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
Conexiones de salida
(IEC C13-10A)*6
(IEC C13-10A)*6
(IEC C13-10A)*6
(IEC C13-10A)*6
(IEC C19-16A)*1
208/230/240 Vac Models
EN 61000-4-2, Level 4
39
Sine wave
0.9
3 to 1
Cables de salida
IEC320 C14-10A
IEC320 C14-10A
IEC320 C14-10A
IEC320 C14-10A
IEC320 C20-10A
EN 61000-2-2