Calibration
A diff erence between the setpoint temperature and the temperature actually measured in the room is
possible, it is generally due to the installation conditions of the heater (location, power / volume, insulation
of the room, ...). Calibration adapts the thermostat setting to actual room conditions.
1 - Place the heater in manual mode on 20 ° C and wait several hours
2 - Measure the room temperature using a thermometer and calculate the diff erence
deviation = measured temperature - setpoint temperature
3 - Set the new value in the Expert Menu (between -3°C and +3°C)
Exemple : After several hours in manual mode with a set temperature of 20°C, I measure the temperature
in the room of 18 ° C. So I have to set a deviation of 18-20 = -2
Automatic drain:
In order to increase the life of the appliance and optimize its operation, an au-
tomatic drain is integrated on the upper part of the frame of the towel heater. It
works in total autonomy and does not require any manipulation by the user.
Using a centralized manager (pilot wire)
The heater can follow the orders of a centralized manager by pilot wire link. Make sure the pilot wire is
connected to the black wire and that Program is inactive.
Confort
Signal à
transmettre
Mesure entre le fi l
0 volt
pilote et le neutre
Load shedding
The heater is compatible with a pilot wire load shedding system. Under no circumstances should a load
shedding by power cut-off be used, which could cause premature wear and damage to electronic boards
which would not be covered by the manufacturer's warranty. During periods of load shedding, the screen
goes to sleep. The device then returns to its original operating mode.
Eco
Hors gel
-115 volts
230 volts
négative
Information on rates operation.
Device identifi cation.
Identication of the software version
Test operation of the heating element.
Arrêt du chauff age
Confort -1°C
Délestage
5'
3"
+ 115 volts
230 volts
positive
pendant 3s
FR
ES
PT
IT
EL
PL
UA
RO
EN
Confort -2°C
5'
7"
230 volts
pendant 7s
117